Briggs & Stratton Standby Generator Fault Codes: What They Mean and What to Do
Is your Briggs & Stratton home standby generator showing “FC” and a number, scrolling a message such as LOW OIL PRESSURE, or blinking its remote light over and over? This guide explains the fault codes on Briggs & Stratton Home Generator System (7–20 kW) and Standby Generator System (15–20 kW) units in plain language. It gives the reset steps from the service manuals, lists the checks that are safe for you to do, and tells you when to call for service.
- We install, service and repair Briggs & Stratton home standby generators
- Fault-code diagnosis, battery, charger and transfer switch service
- Electrical contractor — generator and transfer switch work by one team
- Serving Chicagoland & southeastern Wisconsin
What the display and lights on a Briggs & Stratton generator show
Briggs & Stratton has used two main control panel designs on its air-cooled home standby generators. Which one you have decides how a fault shows up, so take a look at the panel first.
Older Home Generator System models (7, 10, 15, 18 and 20 kW)
These units have a two-position SYSTEM switch (AUTO or OFF), a MANUAL OVER-RIDE button, a SET EXERCISE button, a 15-amp fuse and a small digital display. Normally the display shows a steady number: total run hours. When the controller finds a problem, the display shows FC_ followed by a number from 1 to 8, and for most codes the generator shuts down. An optional remote LED is a light the installer can mount somewhere easier to see. It blinks the same number of times, pauses, and repeats until the code is reset or the problem is corrected. Some systems have an optional StatStation™ screen that spells the fault out in words. The 7 kW and 10 kW manuals note that the panel shows one fault at a time. Once that fault is fixed, the next one, if any, appears. Other models may vary.
Newer Standby Generator System models (15–20 kW)
The current 15–20 kW units use separate AUTO, OFF and MANUAL buttons, menu arrows and a scrolling text display, with the 15-amp fuse under a small cover. In AUTO the display scrolls GENERATOR READY (standing by, utility power present), GENERATOR ON (running during an outage) or SERVICE CODE followed by a description. The manual says codes 1 through 8 also blink an LED sequence. Codes 9 through 16 scroll as text (see the note on code 12 below). If there is more than one code, they are shown one after another. An AUTO LED lights in Auto mode and blinks if the weekly exercise cycle is not set or has been turned off. These units ship with an in-home wireless monitor. Its green GENERATOR READY light keeps blinking during the 20-minute weekly exercise, which is normal.
Steady number or GENERATOR READY
Normal. Older panels show the hour meter. Newer panels show GENERATOR READY in AUTO with utility power present.
FC_ code or SERVICE CODE on the display
A fault. Most codes stop the generator or keep it from starting until the cause is fixed and the code is reset. Write it down.
Remote light blinking in groups
Count the blinks between pauses: one blink is code 1, two is code 2, and so on. It repeats until the code is reset or the problem is corrected.
AUTO light blinking (newer units)
The weekly exercise cycle is not set or has been turned off. Your owner’s manual explains how to set it; call us if you are not sure.
Display is blank
A completely dead battery cannot power the display. Call for service, and do not try to jump-start the unit.
Exact wording varies by model and controller version; your owner’s manual has the details for your unit. The dots above are page markers only, not the color of the lights on your generator.
Shutdown faults vs. codes that do not stop the unit vs. exercise reminders
Shutdown fault Unit stopped
Codes 1 through 7 stop the generator or keep it from starting. They cover low battery, low oil pressure, low output voltage, a failed start, wrong engine speed and high temperature. Your home is not protected during an outage until the fault is corrected and reset.
Code that may not stop the unit Needs attention
The newer manual notes that not every service code shuts the unit down. The clearest example is Fault Code 8 (transfer switch). It is reported only while the unit is stopped in AUTO. It will not stop a generator that is powering your house; it shows up after your house switches back to utility power. Fix it soon.
Exercise and settings reminders Not a fault
A blinking AUTO light on newer units means the weekly exercise is not set. Older units lose the exercise setting when the control panel fuse is removed or the battery is disconnected. After service, a missed exercise often just means the timer needs to be set again. If the unit skips its exercise, check for a fault code first.
Briggs & Stratton fault code list (FC_1 through FC_8)
The eight numbered codes below are shared by the older 7, 10, 15, 18 and 20 kW Home Generator System units and the newer 15–20 kW Standby Generator System. On older panels you see the number; on newer panels you see the name. The blink count is what the remote light shows on the older units; see the note under the table for one difference on the newer units.
| Code (blinks) | Message shown | What it means (in plain words) | What you can do |
|---|---|---|---|
| FC_1 (1 blink) | Low Battery Voltage Fault | Battery voltage fell below the preset level, so there is not enough power to crank the engine. The manuals list a blown fuse in the transfer switch or control panel, a failed battery, something slowly draining the battery, or a failed trickle charger. A completely dead battery leaves the display blank. | Check that your house has utility power; the battery charger only works when it does. Then call us for a battery and charger test. Do not jump-start the unit. |
| FC_2 (2 blinks) | Low Oil Pressure Fault | Oil pressure dropped below about 8 psi (pounds per square inch; the newer manual says 8–10 psi). The oil pressure switch closed, and the controller shut the engine down to protect it. Low oil level, a leak, or a problem with the switch or its wiring can cause it. | With the unit in OFF, look for oil on the pad or under the unit. Do not keep restarting it. Call us to find out why the pressure dropped. |
| FC_3 (3 blinks) | Older: Low Output Voltage / Low Voltage Newer: Under Voltage Fault | The engine ran, but the generator’s output voltage was too low. Common listed causes are too much load, a fuel supply restriction, or the generator’s circuit breaker being open. Others are loose breaker connections, a broken sensing wire (the wire that reports voltage to the controller), or weak engine power. A fault in the alternator (the part that makes the electricity) or the voltage regulator (the part that holds voltage steady) can also cause it. | Turn off large loads (central air, range, dryer). Check your propane level. With the unit in OFF, look at the generator’s circuit breaker only if you can see it without removing a cover or screws. If it is off, switch it ON once. If it trips again, sits behind a cover, or the code returns, call us. |
| FC_4 (4 blinks) | Engine Fails to Start / Engine Does Not Start Fault | The controller cranked the engine in timed tries but never saw it run, so it stopped trying. Older units stop after about two minutes of total cranking. Newer 15–20 kW units stop after six tries. Causes include no fuel, a closed gas valve, or a fuel solenoid (electric fuel valve) that did not open. Starter or wiring trouble, a clogged air filter, worn spark plugs, or an open generator circuit breaker can also cause it. | Make sure the gas valve to the generator is open and a propane tank has fuel. Reset once. If it still will not start, call us. The cranking limit is there to keep the unit from damaging itself, so do not keep retrying. |
| FC_5 (5 blinks) | Low Frequency / Under Frequency Fault | The engine ran too slowly: output fell below 55 Hz for three seconds. Hz (hertz) is how fast the power cycles; it follows engine speed, and normal is about 60 Hz. The controller shuts down to protect the appliances on the transfer switch. Causes include too much load, a restricted air filter, a fuel delivery problem, the governor (the part that holds engine speed steady) or an engine losing power. | Turn off large loads you do not need, then reset once. If it repeats, call us. |
| FC_6 (6 blinks*) | Engine Overspeed / Over Frequency Fault | The engine ran too fast. The controller shuts down after three seconds at 65–70 Hz, or at once above 70 Hz. The manuals point mainly to the governor. On newer units they also list binding throttle linkage and other control or wiring problems. | Call for service. Do not keep resetting an overspeed code; the shutdown protects the appliances wired to the transfer switch. |
| FC_7 (7 blinks) | High Temperature / High Oil Temperature Fault | The engine got too hot (the newer manual gives about 320°F), and the over-temperature switch shut it down. Listed causes: low oil level, a door or the roof left open, blocked air inlets or exhaust, and debris in the engine compartment or on the cooling fins. | Put the unit in OFF and let it cool. Then clear leaves, snow and nests from the outside of the air openings. Do not reach into the exhaust area or touch the muffler. Make sure all doors and the roof are closed and latched. Reset once. If it comes back, call us. |
| FC_8 (8 blinks) | Transfer Switch / Transfer Switch Failure / Transfer Switch Service Code Attention | The controller found an open circuit in the automatic transfer switch — most often a blown fuse inside the switch. See the Fault Code 8 section for the other causes. | Note the code and call us. The transfer switch is a live electrical panel — do not open it. |
Code meanings above summarize Briggs & Stratton service information for air-cooled Home Generator System and Standby Generator System units. Older StatStation-equipped systems display the same faults in words. The newer manual’s code list names code 3 “Under Voltage / Over Voltage”; the display text is Under Voltage. *Blink count note: the 15–20 kW Standby Generator System manual lists five blinks for Engine Overspeed, the same count as Low Frequency. On the newer units, read the scrolling text rather than counting blinks. This page does not cover liquid-cooled or commercial models; call us with the model and serial number from the data plate.
Additional service codes on the newer 15–20 kW Standby Generator System
The current 15–20 kW controller adds numbered service codes 9 through 16. The manual’s code list shows these as text only. However, its Battery Charge Circuit section says code 12 also blinks the light once, the same as Low Battery Voltage. The manual does not say which of these codes stop the generator; it notes only that not all service codes cause a shutdown.
| Code | Message shown | What it means | What you can do |
|---|---|---|---|
| 9 | Over Voltage Service code | Output voltage was too high. The manual uses the same test flow as code 3: a technician checks the breaker output, the sensing wires, the alternator and the voltage regulator. | Call for service. |
| 12 | Battery Charge Circuit Service code | The charging circuit in the control panel is not keeping the battery charged. The manual lists the same causes as Low Battery Voltage. A technician also checks a small fuse on the back of the control board. | Check that your house has utility power, then call us to test the battery and charging circuit. Do not remove fuses yourself. |
| 14 | No Wireless Communication Service code | The control panel lost its link to the in-home wireless monitor. In the manual’s test flow, a technician resets the panel, then tests and relinks the monitor, checks the antenna cable, and replaces the monitor or panel if needed. | Reset once as described below. If it returns, call us to relink or test the monitor. |
| 16 | Generator Sense Failure Service code | The service manual lists this code by name only. | Call for service. |
| 10, 11, 13, 15 | Reserved | Listed as Reserved in the service manual. | If one of these appears, call us with the exact display text. |
Battery and battery charger codes
Low Battery Voltage is fault code 1 on every Briggs & Stratton model covered here. The control panel has a small built-in “trickle” charger. It is a float charger: it keeps a fully charged battery topped up whenever utility power reaches the generator. The manuals say this charger gets its utility power through the fuses in the transfer switch. So a blown transfer switch fuse is one listed reason the battery goes flat.
| Code | Message | What it means | What you can do |
|---|---|---|---|
| FC_1 | Low Battery Voltage Fault | See the FC_1 row in the main table above. | Schedule a battery and charger test. Do not jump-start the unit, remove fuses or disconnect battery cables yourself. |
| 12 (newer units) | Battery Charge Circuit Service code | See the code 12 row in the table above. | Same as above. A technician tests the charger output and current. |
If the code comes back after a reset, the battery or the charger needs testing. A completely dead battery leaves the display blank; do not try to jump-start it from a car. A generator tune-up is a good time to have the battery and charger checked.
Fault Code 8: transfer switch fault
The automatic transfer switch is the box that moves your house from utility power to generator power and back. On these Briggs & Stratton systems, the generator’s control panel watches utility voltage and starts the engine when it drops. On systems that monitor the transfer switch, Fault Code 8 means the controller found an open circuit inside the transfer switch. The manuals list up to four places this can happen. They are the fuses, the contactor coils (the electromagnets that move the switch), the limit switches (small switches inside the transfer switch), and the factory wiring. The older manuals name a blown transfer switch fuse as the most common cause. The newer manual names a blown fuse or wrong dip switch settings as the most likely causes.
This code behaves differently from the others:
- It is reported only while the generator is stopped and sitting in AUTO, not while it runs in exercise or manual mode or powers the house.
- It will not shut the generator down while it is supplying standby power. If the problem happens during an outage, the code appears after power transfers back to utility and the engine stops.
- On every model, this code needs a transfer switch that has monitoring built in. On older Home Generator System units, monitoring is an optional feature that needs a compatible control module in the switch. The newer manual also says the code shows only if the switch is equipped for it. So not every system can show this code.
New installations. Briggs & Stratton service bulletin SB35 describes a second cause on transfer switches with a control board. The dip switches (small settings switches that tell the switch the generator’s size) were set while the switch had power, or were not set correctly. Resetting or even replacing the generator control board will not clear it. The installer has to set the switches correctly, then remove all power from the transfer switch, wait 30 seconds, and restore it so the settings take effect. The newer 15–20 kW manual repeats the same instruction.
How to reset a Briggs & Stratton fault code safely
On every model, putting the unit in OFF does three things: it stops the engine if it is running, keeps it from starting, and clears the fault the controller found. The exact sequence depends on which panel you have. Fix the obvious cause first. The manuals say that if the fault is not corrected, the unit goes back into shutdown and shows the same code.
Older Home Generator System (SYSTEM switch with AUTO / OFF)
- Write down the code (or photograph the display). Then fix the simple cause if there is one: open the gas valve, turn off large loads, or clear debris once the unit has cooled.
- Move the SYSTEM switch to OFF and leave it there for at least 5 seconds.
- Move the SYSTEM switch back to AUTO. If the fault has not been fixed, the same code will come back.
- Reset it only once. If the same code comes back, stop and call us. If a technician had the fuse out or the battery disconnected, the weekly exercise timer needs to be set again.
Newer Standby Generator System 15–20 kW (AUTO / OFF / MANUAL buttons)
- Write down the service code scrolling on the display, then fix the simple cause if there is one.
- Press and hold OFF until the display stops scrolling the service code, then release it.
- Press and hold OFF again for at least 7 seconds until the display turns off.
- Leave it off for at least 30 seconds.
- Press and hold AUTO to return the generator to service. The AUTO light should come on. If utility power is on, the display should scroll GENERATOR READY.
- Reset it only once. If the code returns, call a technician rather than repeating the reset.
Safe checks you can do before you call
Look at the outside
- Leaves, snow, grass or nests blocking the air openings (clear them only with the unit in OFF and cool)
- All access doors and the roof closed and latched
- Plants or stored items too close to the unit
- Oil or fuel on the pad or under the unit
- Chewed wires or animal nests around the base
Check fuel and power
- Gas shut-off valve to the generator is open
- Propane tank has enough fuel
- Your house has utility power (the battery charger needs it)
- Generator circuit breaker is ON, only if you can see it without removing a cover
- The SYSTEM switch or AUTO button is in AUTO, not OFF
Check the panel and monitor
- Note the FC number or the scrolling service code text
- Count the blinks on the remote light, if your system has one
- Note when the code first appeared and whether an outage or storm came before it
- Check whether the weekly exercise has been running
Leave these to a technician
- Removing fuses, or opening the control panel, a breaker cover or the transfer switch
- Battery cables, jump-starting or charging with an outside charger
- Gas pressure, regulator or fuel solenoid checks
- Governor, voltage regulator or alternator testing
- Any code that comes back after one reset
When to call for Briggs & Stratton generator service
- The same fault code returns after one reset.
- You see FC_2 Low Oil Pressure, FC_6 Engine Overspeed, FC_8 Transfer Switch or code 9 Over Voltage — these need a technician every time.
- The generator did not start during an outage, or started but your house did not switch over.
- The display is blank, or the battery code keeps coming back.
- The generator’s circuit breaker trips again after you switch it on once.
- You hear unusual noises, see smoke, or smell fuel or exhaust near the unit.
- The unit has skipped its weekly exercise and you are not sure why.
- It has been more than a year since the last oil and filter change.
GSHA Services installs, services and repairs Briggs & Stratton home standby generators and their automatic transfer switches. Our technicians diagnose fault codes using the Briggs & Stratton service procedures. We test the battery and charging circuit, check fuel supply and pressure, and correct transfer switch problems. We also perform annual maintenance to help catch problems before the next storm. As an electrical contractor, we handle the generator and the electrical side in one visit. Learn more about our generator repair, generator maintenance and whole-house generator installation services. We also service Generac and KOHLER generators.
Request Briggs & Stratton generator service or repair
Tell us the fault code or service code on your display (or the number of blinks on the remote light), the model from the data plate if you have it, and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.
Briggs & Stratton generator service area
GSHA Services is based in Woodstock, IL and services Briggs & Stratton home standby generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.
Frequently asked questions about Briggs & Stratton fault codes
What does FC_1 mean on a Briggs & Stratton generator?
FC_1 is Low Battery Voltage. The battery does not have enough charge to crank the engine. The service manuals list a blown fuse in the transfer switch or control panel, a failed battery, something slowly draining the battery, or a charger that is not working. The built-in charger only works while utility power reaches the generator. Do not jump-start the unit; have a technician test the battery and charger.
How do I reset a Briggs & Stratton generator fault code?
Fix the cause first. On older units with a SYSTEM switch, move it to OFF for at least 5 seconds and then back to AUTO. On the newer 15 to 20 kW units, press and hold OFF until the code stops scrolling, then release it. Press and hold OFF again for at least 7 seconds until the display goes dark. Wait at least 30 seconds, then press and hold AUTO. Reset only once; if the code returns, call for service.
Why does the remote light on my Briggs & Stratton generator keep blinking?
The remote LED blinks the fault code number: one blink for FC_1 Low Battery Voltage, two for FC_2 Low Oil Pressure, and so on up to eight for a transfer switch fault. It keeps repeating until the code is reset or the problem is corrected. One exception: the newer 15 to 20 kW manual lists five blinks for Engine Overspeed, the same as Low Frequency, so read the text on the display too.
What does Briggs & Stratton fault code 8 mean?
Fault Code 8 is a transfer switch fault. The controller found an open circuit inside the automatic transfer switch, most often a blown fuse in the switch. On transfer switches with a control board, dip switches that were set wrong, or set while the switch had power, can also cause it. It only shows while the unit is stopped in AUTO, and it does not shut the generator down while it is powering your house. Do not open the transfer switch; call a technician.
Does my house lose power when the generator shows a fault code?
No. When a fault occurs, the transfer switch automatically returns your home to utility power when it is available. But many fault codes stop the generator or keep it from starting, so it may not run during the next outage until the fault is corrected and reset. Do not leave it that way.
Related generator error code guides
Briggs & Stratton® and StatStation™ are trademarks of Briggs & Stratton or its affiliated companies and are used here only to identify the equipment we service. GSHA Services, LTD is an independent contractor that installs, services and repairs Briggs & Stratton home standby generators. This page is general guidance for homeowners; always follow the safety instructions in your owner’s manual and on the unit.