KOHLER Generator Fault Codes & Warnings: What They Mean and What to Do

Is your KOHLER home standby generator showing a message such as Over Crank or Oil Press Low? Is the OFF light flashing, or did the OnCue Plus app send you an alert? This guide explains what the KOHLER RDC2 controller is telling you, which checks are safe for you to do, and when to call a KOHLER service technician.

In short: a KOHLER RDC2 controller shows a problem as a text message, and in AUTO the OFF light flashes quickly. A warning clears itself; a shutdown stops the generator until you press OFF, then AUTO. Reset it once, and if the message comes back, call for service.
  • Authorized KOHLER dealer
  • Based in Woodstock, IL
  • Service, repair & maintenance on RESV, RESA, RESB/RESC/RESD, RCA and older RES models
  • Serving Chicagoland & southeastern Wisconsin
Safety first. Never open the generator or touch wiring while it is running or set to AUTO — it can start on its own at any time, including for its scheduled exercise. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Never run a generator indoors, in a garage or near an open window, and keep a working carbon monoxide alarm in your home.

How a KOHLER RDC2 controller shows a fault

The KOHLER home standby models on this page use the RDC2 controller. It is the small panel with a two-line text display, RUN, OFF and AUTO buttons, and Select and arrow buttons for the menus. That includes the 8–12 kW RESV, the 14 and 20 kW RESA and RESC, the 20 kW RESB and RESD, and the 14–26 kW RCA. Some “L” models, such as 14RESAL, 20RESAL and 20RESCL units built before 2019, use the DC2 instead. It has RUN, OFF, AUTO and EXERCISE buttons but no menu buttons.

KOHLER introduced a later version, the RDC2.4, in late 2016. There is no separate label: KOHLER identifies it by its blue circuit board and the build date. KOHLER says it operates the same way. The one difference on this page is a longer crank cycle on some 20 and 26 kW models (see Over Crank).

KOHLER does not use numbered codes on these controllers. The display shows a short text message, such as Over Crank or Battery Voltage Low. The same message shows up as an Active Alert in the OnCue Plus app. (On RCA models, KOHLER calls the app KOHLER Energy Management.) The lights above the buttons show the controller’s mode. KOHLER describes them by whether they are on or blinking, not by color:

AUTO light on

Normal. The generator is in standby. The transfer switch — the box that moves your house from utility power to generator power — can call for it at any time. It also starts on its own for its scheduled exercise.

OFF light blinking every 2 seconds

The generator is off. It will not start for an outage, and the exercise will not run. Press AUTO to put it back in standby.

OFF light flashing quickly

A fault shutdown while the unit was in AUTO. The display shows the fault message. The generator will not start again until the cause is corrected and the controller is reset.

A lit RUN light means someone pressed RUN. The generator then ignores the transfer switch until OFF or AUTO is pressed. With a KOHLER Model RXT transfer switch, four more lights show which power source is available and which one is feeding the house. The display backlight turns off after about a minute; press any button to wake it. In AUTO the display cycles through status screens and shows Active Alert when something needs attention.

What you see in OnCue Plus

Open the app and look at Active Alerts. Any current warning or shutdown is listed there. If nothing is wrong, it says No Active Alerts. Tap View Events to see the history, newest first. It includes faults that have already cleared.

In Settings you can turn on email, text or push notifications for warnings, shutdowns and “not in auto.” Exercise and utility-outage messages need a KOHLER Model RXT transfer switch. Maintenance reminders count as warnings, so leave warning notifications on. If the app loses its connection, the generator still works as backup power.

Shutdowns vs. warnings vs. maintenance reminders

Shutdown Unit stopped

The controller stops the engine to protect it. For some faults it runs a short cooldown first. The display shows the fault message, and the OFF light flashes quickly. The generator cannot restart until the cause is corrected and the controller is reset. Your home is not protected from an outage until then.

Warning Needs attention

The generator keeps running or stays ready, but something needs a look — for example, the battery. The controller clears a warning by itself once the condition goes away. If a warning keeps coming back, have it checked before the next storm.

Maintenance reminder Warning

The controller counts engine hours and calendar days. When service is due, it shows Maint Req’d Warning. Book a generator tune-up; we reset the maintenance timer after the service. The controller’s event log also lists informational notices, marked with an “I.”

KOHLER shutdown messages and what they mean

These are the fault shutdowns listed in KOHLER’s manuals for RDC2 and DC2 residential controllers. Names can differ slightly by model, and some are shortened to fit the 16-character screen (for example Eng Speed Low or Engine Speed Low). “After cooldown” means the engine runs briefly to cool before it stops.

Message shownTypeWhat it means (in plain words)What you can do
Over CrankShutdownThe engine cranked three times (15 seconds on, 15 seconds off) and did not start. On 20 kW RESA/RESC and 20 and 26 kW RCA models with RDC2.4 firmware 1.4.4 or later, the controller waits 45 seconds and tries a second round of three. KOHLER’s checks are the fuel supply, spark plug, battery and loose connections.Check that the gas shutoff valve to the generator is open. For propane, check that the tank has fuel. Reset once. If it overcranks again, call us — KOHLER’s manual says the same.
Oil Press Low
Oil Pres Low
Low Oil Level or
Oil Pressure
Shutdown after cooldownThe oil pressure switch reported low pressure for more than 5 seconds while the engine was running. The name depends on the model. 14–20 kW RESA/RESC show Oil Press Low. RESV and 20RESB/D show Oil Pres Low. All 14–26 kW RCA models show Low Oil Level or Oil Pressure. Only the 26RCA also has an oil level switch; on the other models this is not a low-oil-level alarm. KOHLER’s checks are oil leaks, the oil level, and the pressure switch and its wiring. In freezing weather, moisture and frost on the sensor can also cause false trips.With the unit in OFF, look for oil on the ground under the unit. Do not keep restarting it. Call us — a technician checks the oil level and the pressure switch.
Emerg Stop ShutdwnShutdownThe optional red emergency stop button was pressed. Or the engine shutdown switch on the generator was set to O (off), which is done during service.First find out who pressed it and why — it may have been pressed on purpose. KOHLER says to reset it only after you confirm it is safe for the generator to start and power the house. Then remove any lock, pull the red button out, and press OFF, then AUTO. If nobody pressed it, call us.
Eng Speed High /
Frequency High
Shutdown after cooldownThe engine ran more than 15% over normal speed. Or the output frequency stayed more than 10% high for 10 seconds. (Frequency is the steady 60-cycle rhythm of household power.) KOHLER’s manuals give no owner check for this one; they say to contact a dealer.Call for service.
Eng Speed Low /
Frequency Low
Shutdown after cooldownEngine speed fell below 85% of normal for 3 seconds. Or frequency stayed 10% low for 10 seconds, or 1 Hz low for a minute. KOHLER’s first check is overload. On models with an enclosure thermostat (20RESB, 20RESC, 20RESD, RESV and RCA), the thermostat may have tripped because the cabinet got too hot (see overheating).Turn off large appliances you don’t need. Clear leaves, snow or debris from the air inlets and outlets. Reset once. If it repeats, call.
Volts L1-L2 High / LowShutdown after cooldownOutput voltage went more than 20% above normal for 2 seconds (High), or more than 20% below normal for 10 seconds (Low). For Low, KOHLER’s checks are overload and, on models with an enclosure thermostat, a tripped thermostat. Anything beyond that is technician work.For Low: reduce the load and reset once. For High, or if Low repeats: call.
AC Sens LossWarning or ShutdownIn AUTO, the controller lost the signal that shows the generator is making power. It starts checking 10 seconds after the engine starts. There are two separate cases. If no output shows up at all, you get a warning after 1 second. If output was there and then disappeared, the unit shuts down after 3 seconds. A technician checks the wiring and the alternator (the part that makes the electricity).Call for service.
Spd Sens FltShutdownThe engine speed signal was lost. KOHLER lists two causes: the speed sensor failed, or the engine stalled.Call for service.
Locked RotorShutdownThe starter was told to crank, but the controller sensed no engine rotation. It shuts down 3 seconds after it detects this. KOHLER’s checks are the battery and loose connections. Beyond that, a technician checks the cranking circuit and the engine.Do not keep trying to start it. Call for service.
MainPwrOverLShutdownThe controller’s built-in circuit protection tripped from a short circuit on its main power output.Press OFF to reset — once. Then call us to find the short.
Alt Protect /
Total Power High
Shutdown10RESV and 12RESV only. The generator saw high current, or the load stayed above 102% of its rating for more than a minute. It stopped to protect the alternator from overheating.Turn off big loads (AC, range, dryer, well pump) and reset once. If it happens often, ask us about load management.

Meanings above summarize the fault tables in KOHLER operation and service manuals for RDC2/DC2 residential generators (8–26 kW). Three-phase units, larger liquid-cooled models and paired (paralleled) generators can show more messages. Call us with the model and serial number from the nameplate.

Warning messages: battery, exercise and transfer switch

Warnings do not stop the generator. The controller clears them on its own once the condition goes away. Still, don’t ignore one. Battery warnings matter most: the controller checks battery voltage before each exercise to judge whether the engine can start.

Message shownTypeWhat it meansWhat you can do
Battery Voltage Low
(Battery Low on RESV
and 20RESB/D)
WarningThe starting battery has stayed below 12.5 volts for 90 seconds while the engine was not running. The RDC2 charges the battery with its built-in charger. That charger is fed from your house on a breaker-protected circuit. If that circuit is off, the charger cannot keep the battery up.Check the breaker in your electrical panel labeled for the generator. If it is not tripped, call us to test the battery and charger.
Battery CrLo WarningWarningBattery voltage fell below 11 volts for more than 10 seconds (KOHLER’s RESV service manual says 30 seconds). It is checked any time except while the starter is cranking. This is a more serious version of Battery Voltage Low. KOHLER’s fix is to charge or replace the battery.Call soon to have the battery and charger tested.
Lo Crank VltWarningBattery voltage dropped too low while the starter was cranking. The exact limit varies by model. KOHLER’s fix is to charge or replace the battery.Have the battery and its connections tested.
Battery High
(Battery Voltage High
on RCA)
WarningBattery voltage rose above 16 volts for more than 10 seconds. KOHLER’s checks are the battery’s rating and condition and the battery charger.Call for service.
Low Coolant LevelWarningStrange but true: on air-cooled 14 and 20 kW RESA/RESC models, this message points to a battery voltage supply problem, not coolant.Check the generator’s breaker in your electrical panel. If it is on, a technician checks the power supply to the generator and the battery connections.
Not in AutoWarningSomeone pressed OFF or RUN. The generator ignores the transfer switch, and the exercise will not run.Press AUTO when it is safe to do so. If you did not press OFF or RUN, find out who did.
Exer Not SchWarningNo exercise is scheduled on the controller. When the controller’s power is disconnected and reconnected, it asks for the date, time and exercise settings again.Set the exercise at the controller or in OnCue Plus. Or ask us at your next visit.
Maint Req’d WarningWarningEngine hours or calendar days have passed the maintenance interval.Schedule maintenance. We reset the timer after the service.
ATS ComErrorWarningThe controller lost communication with the interface board in the KOHLER RXT transfer switch.A technician checks the communication wiring between the generator and the switch.
GenBrkerOpen WarningWarningShown only with a KOHLER RXT transfer switch. The generator is making power, but none is reaching the transfer switch. KOHLER’s service manual points to the generator’s own line circuit breaker. It may have tripped from an overload or a short on the house side.Press OFF and turn off large appliances you don’t need. Then call us. A technician checks for a short or overload before resetting that breaker.
Oil Temperature HighWarning / ShutdownRESV models: oil above 300°F is a warning; above 325°F the unit shuts down. KOHLER’s checks are blocked air inlets and a dirty air cleaner.With the unit in OFF, clear anything blocking the vents. If it repeats, call.

Other messages you might see

  • Chk DateTime Warning – controller power was interrupted, so the date and time may be wrong. Check the date and time, and make sure an exercise is still scheduled.
  • ATS Fail Xfr, Accy PwrOver, Oil Pressure OpenCR – the transfer switch failed to transfer, a short on the controller’s accessory output, or a bad oil pressure switch circuit. Call.
  • Aux Input, Batt Chg Flt, Fuel Level, Ground Fault – these come from equipment wired to the optional Programmable Interface Module (PIM), such as an external charger or tank sensor. A technician checks that equipment.

Overheating and the enclosure thermostat

Many homeowners expect a “high engine temperature” alarm. RDC2 generators handle heat a little differently. The manuals mention a high-temperature switch that resets itself once the engine cools. But for most models, the fault lists on this page have no separate high-temperature message. RESV models are the exception: they can show Oil Temperature High.

Models with an enclosure thermostat — 20RESB, 20RESC, 20RESD, 8–12 kW RESV and 14–26 kW RCA — have a thermostat inside the cabinet. It trips when the enclosure gets too hot. The generator shuts down, and the display shows an underspeed, underfrequency or undervoltage fault. OnCue Plus may name high engine temperature in a shutdown notice, and older controllers show HE.

Whatever the message, the safe first step is the same, and it is KOHLER’s first check too. With the unit in OFF, clear leaves, snow, grass clippings, nests and plants from the air intake and exhaust sides of the enclosure. Resetting the thermostat itself is a technician job. Every KOHLER procedure starts by turning off the generator’s breaker in the house panel. Then the roof is opened, and on most models a panel is removed. Some models also need the battery disconnected. If the fault comes back after one reset, call.

Older KOHLER controllers: ADC-RES and RDC/DC codes

Older 8.5–18 kW RES units use the ADC-RES controller. Older 14 and 20 kW RES units use the RDC or DC controller. Instead of a text message, these show a short letter code. On the ADC-RES, the code flashes on a small LED display. The ADC-RES also has a three-position master switch: RUN, OFF/RESET and AUTO.

CodeFaultControllerWhat you can do
OCOvercrank: three failed start attempts (on the ADC-RES, OC also shows if the engine does not turn over while cranking)ADC-RES, RDC/DCCheck the gas valve and propane level; reset once; call if it repeats.
LOPLow oil pressure shutdownADC-RES, RDC/DCWith the unit OFF, look for oil leaks under it; call.
HEHigh engine temperature (RDC: warning at 300°F, shutdown at 325°F)ADC-RES, RDC/DCClear blocked air inlets and exhaust outlets; call if it repeats.
AFAuxiliary fault: the emergency stop was pushed (ADC-RES, TRES models only) or a customer-wired input closed (RDC/DC)ADC-RES (TRES only), RDC/DCFind out why the stop was pushed before resetting it. On TRES models the stop knob is turned clockwise to release it. If you are unsure, call.
LrLocked rotor: the engine did not turn while crankingRDC/DC only (the ADC-RES reports this as OC)Do not keep trying; call.
OS, OF, OU, UF, UUOver/under frequency and voltage, overspeedADC-RES, RDC/DCFor UF or UU reduce the load and reset once; otherwise call.
USUnderspeedRDC/DC onlyReduce the load and reset once; call if it repeats.
HB / LBHigh / low battery voltage warnings (shown as Hb / Lb on RDC/DC)ADC-RES, RDC/DCCheck the generator breaker in your panel; have the battery and charger tested.
LCbLow cranking voltage warningRDC/DC onlyHave the battery tested; KOHLER’s fix is to charge or replace it.
AC, ATS, SS, ESch, NoECLoss of AC sensing; lost connection to the transfer switch (a shutdown with a KOHLER RRT switch); speed sensor failure; exercise not scheduled; controller settings lostRDC/DCESch: set the exerciser. Others: call. KOHLER says not to replace the controller for NoEC; a technician re-enters the settings.

To reset an ADC-RES after a shutdown, KOHLER’s procedure starts with the master switch at OFF/RESET and ends by returning it to AUTO. The steps in between are technician work. The RDC/DC procedure is similar: it starts with pressing OFF and ends with pressing AUTO. In between, the unit is taken off the load, the cause is fixed and the unit is test-run. That is technician work too. On the RDC/DC, pressing OFF clears the ESch warning. Other older KOHLER controllers use their own codes — check your owner’s manual or call us with the model number.

How to reset a KOHLER fault safely

  1. Write down the message, or take a photo of the display or the OnCue Plus alert. It helps our technician bring the right parts.
  2. Fix the obvious cause first. Open the gas valve, check the propane tank, clear debris from the vents, or turn off large loads. Check the generator’s breaker in your electrical panel. If the display shows Emerg Stop Shutdwn, find out why the stop was used before you reset anything (see above).
  3. Press OFF. On RDC2 and DC2 controllers, the OFF button clears the fault and resets the controller. (On the RDC2 you can also use the menu. Press Select three times until Confirm Clear Fault: NO shows. Use the arrow buttons to change it to YES. Press Select twice, and the controller goes to OFF.)
  4. Press AUTO. The AUTO light should come on, the OFF light should stop flashing, and the display should return to its status screens with no Active Alert.
  5. Reset it only once. KOHLER’s manuals say to find and correct the cause of a shutdown before resetting. Our advice at GSHA: if the same message comes back, stop and call a KOHLER technician.
Remember: while the generator is in OFF, or a shutdown is active, your home is not protected during a power outage, and the scheduled exercise will not run. Don’t leave it that way — get it back to AUTO or call us.

What the exercise run checks

KOHLER’s RDC2 manuals call for exercising the generator every week or every two weeks. RCA models can also be set to exercise monthly. The 26RCA adds a short 90-second EcoExercise, which KOHLER recommends monthly in cold climates. The controller runs the exercise on its own, on the day and time you set, but only when it is in AUTO.

The default Unloaded Cycle exercise with diagnostics lasts about 20 minutes. The engine runs at reduced speed for 10 minutes. Then it ramps to full speed for 3 minutes of self-tests on the engine and the power output. It ends with a 5-minute cooldown. Because of these tests, a problem can show up on a quiet afternoon instead of during a storm.

What if the unit shuts down on a fault during an exercise? Newer firmware tries to restart the engine. If it starts, it runs at full speed for two minutes and then stops (the event history shows Advanced Diagnostic Active). If it cannot restart, the shutdown message stays on the display.

Safe checks you can do before you call

Look at the outside

  • Leaves, snow, grass or nests blocking the air inlets or exhaust outlet
  • Plants or objects too close to the unit
  • Signs of animals chewing wires
  • Oil or fuel leaks under the unit

Check fuel and power

  • Gas shutoff valve to the generator is open
  • Propane tank has enough fuel
  • Generator breaker in your electrical panel isn’t tripped (it feeds the battery charger)
  • Red emergency stop button, if fitted: if it is pushed in, find out why before resetting it

Check the controller and app

  • AUTO light is on, not the OFF or RUN light
  • Read the Active Alert on the display or in OnCue Plus
  • Check View Events for when the problem started
  • Confirm an exercise is scheduled

Leave these to a pro

  • Opening electrical panels or covers, fuses or wiring
  • Checking or adding engine oil
  • Resetting the generator’s own line circuit breaker
  • Gas pressure, regulator or fuel line work
  • Resetting the enclosure thermostat
  • Transfer switch problems
  • Any fault that repeats

When to call a KOHLER service technician

  • The same fault comes back after you reset it once.
  • You see Oil Press Low (or Oil Pres Low, or Low Oil Level or Oil Pressure), Eng Speed High, Volts L1-L2 High, AC Sens Loss, Spd Sens Flt, Locked Rotor, MainPwrOverL or GenBrkerOpen.
  • The generator didn’t start during an outage, or started but your house never switched over.
  • A battery or charger warning keeps returning, or Battery CrLo appears.
  • You hear unusual noises, see smoke, or smell fuel.
  • Maint Req’d is showing, or you are not sure when the generator was last serviced.

As an authorized KOHLER dealer, GSHA Services diagnoses, repairs and maintains KOHLER home standby generators. Scheduled maintenance lets us find small problems on a planned visit instead of during an outage. Learn more about our KOHLER generator service, generator repair, generator maintenance and whole-house generator installation. We also service Generac and other brands.

Request KOHLER generator service or repair

Tell us the fault message on the display or in the app, your generator model (from the nameplate if you have it) and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

KOHLER service area

GSHA Services is based in Woodstock, IL and services KOHLER generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions about KOHLER fault codes

Why is the OFF light flashing on my KOHLER generator?

If the OFF light flashes quickly while the generator is in AUTO, the controller has shut the generator down on a fault. The display shows the fault message, such as Over Crank or Oil Press Low. Fix the cause if it is something simple, then press OFF and AUTO once. A slower blink every two seconds means the generator is simply in OFF and will not start for an outage. Press AUTO.

How do I reset a KOHLER generator after a fault shutdown?

On an RDC2 or DC2 controller, press the OFF button to clear the fault. Then press AUTO to put the generator back in standby. On the RDC2 you can also clear it through the menu. Press Select three times until Confirm Clear Fault: NO appears. Use the arrow buttons to change it to YES, press Select twice, then press AUTO. Only reset once. If the same fault returns, call for service.

What does Over Crank mean on a KOHLER generator?

Over Crank means the engine tried to start three times and did not run. Check that the gas valve to the generator is open and that a propane tank is not empty, then reset once. If it overcranks again, call a technician. KOHLER’s own checks are the fuel supply, spark plug, battery and loose connections.

What does Oil Press Low mean on a KOHLER generator?

Oil Press Low means the oil pressure switch reported low pressure for more than five seconds while the engine was running, so the controller shut the engine down to protect it. RESV and 20RESB/D models show it as Oil Pres Low. RCA models show Low Oil Level or Oil Pressure; only the 26RCA also has an oil level switch. With the generator in OFF, look for oil leaks under the unit. Do not keep restarting it. Call for service so a technician can check the oil level and the pressure switch.

What does Battery Voltage Low mean on a KOHLER generator?

The starting battery has stayed below 12.5 volts for 90 seconds while the engine was not running. RESV and 20RESB/D models show this as Battery Low. The warning clears by itself when the voltage recovers. First check that the breaker in your panel that feeds the generator’s built-in battery charger is not tripped. If the warning keeps returning, have the battery and charger tested.

Related generator error-code guides

KOHLER® is a registered trademark of Kohler Co.; KOHLER generators are a Rehlko business. OnCue® is a trademark of its respective owner. GSHA Services, LTD is an authorized KOHLER dealer. This page is general guidance for homeowners; always follow the safety instructions in your owner’s manual and on the unit.