← All home generator error codes
Cummins® Home Standby · Install, Service & Repair

Cummins Home Standby Generator Fault Codes: What They Mean and What to Do

Is the red ACTION REQUIRED light on your Cummins in-home panel, or is the screen showing a “Fault” with a code number? This guide covers the fault codes and warning messages on Cummins RS13A, RS14AF, RS20A/RS20AC and GSAA 12 kW home standby generators. It explains them in plain language, shows which checks are safe for you to do, and tells you when to call a generator technician.

  • We install, service and repair Cummins home standby generators
  • Generator, transfer switch and electrical work by one team
  • Based in Woodstock, IL
  • Serving Chicagoland & southeastern Wisconsin
In short: on a fault shutdown, the red ACTION REQUIRED lamp comes on and the in-home panel shows the fault name and a fault code number. Fix the simple cause if there is one — a closed gas valve or too many appliances running — then clear the fault and turn Standby back ON once. If the code comes back, or it is code 2 (Low Oil Pressure), leave Standby off and call us.
Safety first. A Cummins standby generator can start on its own at any time while it is in standby. Never open the housing or touch wiring unless a technician has made the unit safe. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Engine exhaust contains carbon monoxide — never run a generator in or near a garage or open window, and keep a working carbon monoxide alarm in your home. Cummins also warns that these generators are not for life support and can stop without warning, so have a backup plan for medical equipment.

What the lights on the Cummins in-home panel mean

Cummins RS-series and GSAA home standby generators are controlled from a wall-mounted in-home Operator Panel that is hard-wired to the generator. It has two UTILITY lamps, three GENERATOR lamps, three buttons (BACK, STANDBY ON/OFF and START STOP) and a small screen with four navigation buttons. Some homes also have the optional internet/email interface, which shows the same information in a web browser and can send email alerts. Here is what each lamp tells you:

UTILITY PRESENT (green)

Utility power is available at the transfer switch — the box that moves your house between utility power and generator power.

UTILITY CONNECTED (green)

Your home is running on utility power. Both green UTILITY lamps on and “Genset Stopped” on the screen means everything is normal.

GENERATOR RUNNING (green)

The generator has started. When it takes over the house, UTILITY CONNECTED goes out and the screen shows “Genset Load” bar graphs for the two supply lines (L1 and L2).

STANDBY OFF (red)

The generator will not start on its own if utility power fails. This lamp comes on after a fault shutdown, after any manual start or stop, or if someone turned standby off. See how to turn it back on.

ACTION REQUIRED (red)

Either the generator shut down on a fault or scheduled maintenance is due. The screen tells you which one.

The screen also shows whether the generator is stopped or running (“Genset Stopped” or “Genset Running”). On the GSAA 12 kW panel the home screen also shows the battery voltage (for example “Battery 12.5”) and the time; the RS-series operator manuals do not describe a battery readout, so not every panel has one. Inside the generator housing there is a separate small status light on the control switch that flashes fault codes — more on that below.

Lamp names and screens above come from the Cummins operator manuals for the RS13A (model GSBA), RS14AF/RS20A/RS20AC (models GSBB and GSBC) and the GSAA 12 kW. Your panel or software version may differ slightly.

Fault shutdowns vs. warnings vs. maintenance reminders

Fault shutdown Red – unit stopped

The controller stopped the engine, or refused to start it, to protect the generator. The screen shows “Fault”, a short description, the fault code number and when it happened. Cummins turns Standby off after a fault shutdown, so the generator stays off until you clear the fault and re-enable standby. Your home is not protected until then.

Warning Logged – needs attention

A logged problem that does not show a fault code. Warnings are recorded in the Event Log, for example Low Battery or Battery Charger Failure, Transfer Switch Signal Failure or Transfer Switch Failed to Transfer to Utility. Have them looked at before the next outage.

Maintenance reminder Red ACTION REQUIRED

A Maintenance Due screen appears when a scheduled service is due and it does not go away on its own. The Event Log records what is due. One example is “Change oil and check valve lash” (valve lash is a small engine adjustment). Another is “Change oil & filter, air filter, adjust valve lash, clean and check battery & engine cooling fins.” Book a generator tune-up.

Cummins home standby generator fault code list

Cummins home standby controllers use single-digit and two-digit shutdown codes. The in-home panel shows the code, and the status light inside the generator flashes it. Most codes apply to every model on this page. Code 1 is listed only for the RS-series units, code 38 only for the GSAA 12 kW, and code 74 only in the RS-series service manuals. Find your code below.

CodeFault shownWhat it means (in plain words)What you can do
1High engine temperature (1 blink)
Shutdown RS-series only
One blink on the status light means the engine shut down because it got too hot. The GSAA 12 kW manuals do not list this code.Call for service.
2Low Oil Pressure
Shutdown
Oil pressure was lost, so the engine shut down to protect itself. Cummins lists an oil level that is too low or too high, a faulty oil pressure switch, the relief valve or the oil pump.Leave Standby OFF until the oil has been checked, so the engine does not restart low on oil. The first step in the manual is to check the oil level and add or drain oil. A GSHA technician does this after making the unit safe.
3Service Check
Shutdown
Not a fault on its own. Three blinks on the generator’s light means a two-digit fault caused the shutdown.Read the real code on the in-home panel (Fault screen or Fault Log), then look it up in this table.
4Overcrank
Shutdown
The engine cranked through its full set of start attempts (three tries) and never ran. Causes listed include the fuel supply, the fuel and air going into the engine, the exhaust, ignition, the starter, wiring and the start switch.Make sure the gas shut-off valve to the generator is open. If you use propane, check the tank. Cummins says a vapor-withdrawal propane tank should be at least half full when it is below 40°F outside. Then call us. Spark plugs, air filter and fuel pressure are technician checks.
12Overvoltage
Shutdown
Generator output voltage went too high. Causes listed: the house loads, wire connections or the alternator (the part that makes the electricity).Call for service.
13Undervoltage
Shutdown
Output voltage stayed too low. Causes listed: the house loads, wire connections or the alternator.Call for service.
14Overfrequency
Shutdown
The engine ran too fast. Causes listed include the load, the engine’s speed control (the governor), the fuel and air supply, other engine parts, the alternator and wiring.Call for service.
15Underfrequency
Shutdown
The engine could not hold its normal speed. Too much load is one possible cause. Others include the speed control (governor), the fuel and air supply, other engine parts and wiring.Reduce the number of appliances running, especially air conditioners and others with a big starting surge. If it repeats, call us.
19Governor Actuator Shutdown
Shutdown
The circuit to the governor actuator (the part that controls engine speed) is open or shorted.Call for service.
22Governor Actuator Overload
Shutdown
The governor worked at or near its limit for too long trying to hold speed. Causes listed include too much load, the fuel and air supply, the exhaust, the actuator, ignition and wiring.Reduce the load on the generator. Then call us — the air filter and fuel supply are technician checks.
27Voltage Sense Lost
Shutdown
The controller could not see the output voltage on one or both lines while the engine was running.Call for service.
29High Battery Voltage
Shutdown
Battery voltage to the controller is too high. Causes listed: wrong battery setup, wire damage, a faulty charger or the control.Call us — the battery charger needs to be tested.
32Low Cranking Speed Sense
Shutdown
The engine turned over too slowly when the controller tried to start it. Listed causes include the battery and its connections, engine oil that is too thick for the outdoor temperature, the starter, other engine parts and wiring.Call for service. A technician cleans and tightens the battery connections, tests the battery, and makes sure the oil is the right type for the temperature.
35Control Card Failure
Shutdown
The controller failed its own self-test (stored program error).Call for service.
36Stopped Without Fault Condition
Shutdown
The engine stopped by itself with no other fault recorded. Causes listed include the fuel supply, the fuel and air system, the exhaust, ignition, the alternator and wiring.Check that the gas valve is open and a propane tank is not empty. Then call us.
37Invalid Set Configuration
Shutdown
The controller’s settings do not match a valid generator configuration.Call for service. A technician resets and saves the configuration from the display, or replaces the control if it will not clear.
38Field Overload (Overvoltage)
Shutdown GSAA 12 kW
Listed for the GSAA only. Cummins gives “low power factor” loads, such as air conditioners, as the cause.Reduce the load, especially air conditioners. If it repeats, have the appliances checked and call us.
43Processor Fault
Shutdown
The controller failed its memory self-test.Call for service. A technician power-cycles the control and replaces it if the fault returns.
45Speed Sense Fault
Shutdown
The controller lost the engine speed signal while running. Causes listed: loads, the alternator, wiring.Call for service.
46Generator Set Overload
Shutdown
Your home is drawing current at or above the generator’s design limit. The generator was close to shutting down on undervoltage (13), underfrequency (15), governor overload (22) or an unexpected stop (36).Turn off large appliances. If it keeps happening, ask us about load management. These controllers can be set up to disconnect certain large loads, such as air conditioners, when relays are installed.
74Control Board Not Programmed
Shutdown RS-series
The control board has no software loaded. Found on RS-series units.Call for service — the control needs its software loaded.
76Alternator Over Temp
Shutdown
The alternator got too hot. Causes listed: blocked intake or exhaust openings, the cooling fan, the temperature sensor, wiring.On RS-series units, Cummins lists clear air openings as a first check. Confirm the red STANDBY OFF lamp is lit and let the unit cool. Then clear leaves, snow or debris from the outside of the housing only, and make sure the housing is closed and latched. If it returns, or you have a GSAA 12 kW, call us.
78Low Fuel Pressure
Shutdown
The fuel pressure switch reported low gas pressure. Causes listed: the fuel system, the pressure switch, wiring.Open any closed fuel valves and check your propane level. Then call us — gas pressure and regulators are technician checks.
79Failure to Transfer to Generator Set
Shutdown
The controller told the transfer switch to move to generator power but did not get a confirmation within its 5-second delay. Causes listed: wiring, the position switch, transfer switch parts.Call for service. A technician first verifies that the generator’s main AC breaker is on, then checks the transfer switch wiring and position switch.

Code meanings above summarize the Cummins operator and service manuals for the RS13A, RS14AF/RS20A/RS20AC and GSAA 12 kW home standby generators. Exact trip points and wording vary by model and software — check your owner’s manual. This page covers these models only; for other Cummins models, call us with the model and serial number from the nameplate.

Inside the generator housing, the control switch has a small status indicator light. When a fault shuts the unit down, this light flashes the code over and over. A two-digit code flashes the tens digit, pauses, then flashes the ones digit. For example, fault 36 is three flashes, a pause, then six flashes. What the single flashes mean depends on your model.

RS13A, RS14AF and RS20A/RS20AC (models GSBA, GSBB and GSBC)

  • 1 blink – shutdown from high engine temperature.
  • 2 blinks – shutdown from loss of oil pressure.
  • 3 blinks – a “service fault” with a two-digit code behind it. A technician can press Stop once to make the two-digit code flash, and press Stop again to end it.
  • 4 blinks – the engine cranked too long without starting (overcrank).

On these models, codes 1 through 4 are “first level” faults and the rest are “second level.” Codes 33 and 44 are not used, so they cannot be confused with 3 and 4. The blinking stops after five minutes. A technician can bring it back by pressing Stop three times within three seconds. The last fault keeps blinking even after its cause has been fixed, so a blinking light by itself does not mean the problem is still there.

GSAA 12 kW

The GSAA manuals describe 2 flashes (low oil pressure), 3 flashes (a two-digit code is behind the shutdown) and 4 flashes (overcrank), plus two-digit codes. They do not describe a one-blink high-temperature code, the five-minute timeout or the three-press restore.

You do not need to open the housing to get the code. The in-home panel shows the same fault, and the Fault Log (MENU › Fault Log › ENTER) keeps the last five faults with their codes, dates and times. Leave the housing closed and let a technician read the light if needed.

Battery, charger and other problems that do not show a code

Not every Cummins problem produces a fault number. These messages and symptoms come from the operator manuals’ troubleshooting sections and event lists.

Message or symptomWhat it meansWhat you can do
Low Battery or Battery Charger Failure
Warning
The starting battery is low, or the charger (mounted in the transfer switch on these systems) is not charging it.If your panel shows a battery voltage on its home screen (the GSAA 12 kW panel does), note the reading. Then schedule a battery and charger test. Cummins lists clean, tight battery connections among the habits that lower the chance of a shutdown.
Starting battery keeps running downCauses listed: marginal battery connections, the battery itself, the charging system, excessive cranking. Cummins says to have the charger in the transfer switch serviced or replaced if the battery keeps running down.Call us. Battery cables and the charger are technician work.
No response, status light deadLittle or no battery voltage, a poor battery connection, an open harness connection, a faulty switch or light.Call for service.
Starter engages and disengagesBattery voltage dips too low while cranking, so the controller gives up. Causes listed: battery connections, battery, charging system, switches.Call for service.
No power in the house while the generator is running
(status light on steady or flashing rapidly)
A circuit breaker tripped from an overload or a short.Turn off large appliances and check for a tripped breaker in your home’s electrical panel. The generator’s own main breaker is inside the housing — we check that one.
Transfer Switch Failed to Transfer to Utility
Warning
Utility power is back but the transfer switch did not move the house back to it. Cummins lists a faulty transfer switch or a disconnected or broken wire.Call us. The transfer switch and its control wires need an electrician.
Transfer Switch Signal Failure
Warning
The controller cannot see either position wire from the transfer switch — broken wiring or a switch stuck between positions.Call us.
Utility lost – not in Standby Ready
Event
The power went out while standby was turned off, so the generator did not start.Turn Standby ON (see below) so it starts next time.
Generator starts or stops on its own, no codeCauses listed: low battery voltage, a shorted harness, a faulty switch. A scheduled exercise run is normal and is not a fault.Check the Event Log for “Genset exercise started.” If it was not an exercise, call us.

How to clear a Cummins fault and get back to standby

  1. Write down the fault name, code number and the time or hour reading shown, or take a photo of the panel. The Fault Log keeps the last five faults if the screen has already changed. This helps our technician arrive with the right parts.
  2. Fix the obvious cause first — open the gas shut-off valve, check the propane level, or turn off big appliances. If leaves or snow block the air openings, confirm the red STANDBY OFF lamp is lit and let the unit cool, then clear them from the outside only. Do not open the generator housing. For Low Oil Pressure (code 2), stop here: leave Standby OFF and call us so the oil can be checked first.
  3. Press BACK on the Fault screen. On RS13A, RS14AF and RS20A/RS20AC panels, this resets the fault and returns you to the home screen. The GSAA 12 kW manual does not say what BACK does on the Fault screen, so check your operator manual or call us.
  4. Turn Standby back ON. After a fault shutdown the red STANDBY OFF lamp is lit. Press STANDBY ON/OFF, use the arrow buttons to select ON, then press BACK. The STANDBY OFF lamp goes out and the screen says “Standby ready enabled by user.” The switch on the generator itself must also be in its automatic position (called Remote on RS-series units). That switch is inside the housing, so if you think it was moved, call us instead of opening the unit.
  5. Clear it only once. If the same code comes back, or ACTION REQUIRED lights up again, stop and call a generator technician. Do not keep restarting it.
Remember: while STANDBY OFF is lit or a fault is active, your home is not protected during a power outage. Do not leave it that way — get standby back on or call us.

Safe checks you can do before you call

Do these checks from outside the generator housing. Before you clear anything near the unit, confirm the red STANDBY OFF lamp is lit on the in-home panel (it comes on after a fault shutdown) and give the generator time to cool if it ran recently.

Look at the outside

  • Leaves, snow, grass or nests on the air inlet and outlet screens — clear them from the outside only
  • Plants or stored items too close to the unit
  • Signs of animals chewing wires
  • Oil or fuel stains under the unit
  • Housing closed and latched

Check fuel and power

  • Gas shut-off valve to the generator is open
  • Propane tank level — Cummins wants vapor-withdrawal tanks at least half full when it is below 40°F
  • No tripped breakers in your home’s electrical panel

Check the in-home panel

  • Which lamps are lit — especially STANDBY OFF and ACTION REQUIRED
  • The battery voltage, if your panel shows one on the home screen
  • The Event Log (last 20 events) and Fault Log (last 5 faults)
  • Whether the last scheduled exercise ran

Leave these to a pro

  • Opening the housing or touching the battery cables
  • Checking or adding engine oil
  • Gas pressure, regulators and fuel lines
  • Transfer switch and control wiring
  • Controller settings and software
  • Any fault that repeats

When to call a Cummins generator technician

  • The same fault code comes back after you cleared it once.
  • You see an electrical or controller fault: 12, 13, 14, 19, 27, 29, 35, 37, 43, 45 or 74. There is no homeowner fix for these.
  • You see High Engine Temperature (1), Low Oil Pressure (2), Overcrank (4) or Low Cranking Speed (32). Do not keep trying to start it.
  • The generator started but the house did not switch over, or you see code 79 or a transfer switch warning.
  • A Low Battery or Battery Charger Failure warning does not go away.
  • The Maintenance Due screen is showing, or service is overdue on the schedule in your operator manual.
  • You hear unusual noises, see smoke, or smell fuel.

GSHA Services installs, services and repairs Cummins home standby generators and their automatic transfer switches. We handle the electrical side too — transfer switch wiring, panel connections and load management — so one visit can cover the whole system. Cummins says warranty work must go through its own dealer network. If your problem looks like it may be covered, we will tell you so you can decide how to proceed. We also service Generac, KOHLER and Briggs & Stratton units. Learn more about our generator repair, generator maintenance and whole-house generator installation services.

Request Cummins generator service or repair

Tell us the fault code or message on your panel, your generator model (from the nameplate if you have it) and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Cummins generator service area

GSHA Services is based in Woodstock, IL and services Cummins home standby generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions about Cummins fault codes

What does the red ACTION REQUIRED light on a Cummins generator panel mean?

ACTION REQUIRED means the generator shut down on a fault or scheduled maintenance is due. The screen on the in-home panel tells you which. For a fault, it shows a short description, a fault code number and when it happened. Look the code up in the table on this page and fix the simple cause if there is one. Then clear the fault and turn Standby back ON once, using the steps on this page. If it comes back, call a generator technician.

What does Cummins fault code 4 (Overcrank) mean?

Code 4 means the engine cranked through all of its start attempts but never ran. Causes listed include the fuel supply, the fuel and air going into the engine, the exhaust, ignition, the starter, wiring and the start switch. Make sure the gas shut-off valve to the generator is open. If you use propane, check the tank. Cummins says a vapor-withdrawal propane tank should be at least half full when it is below 40 degrees F outside. Then call for service. Spark plugs, air filter and fuel pressure are technician checks.

What does Cummins fault code 2 (Low Oil Pressure) mean?

Code 2 means the engine shut down because oil pressure was lost. The manual lists an oil level that is too low or too high, a faulty oil pressure switch, the relief valve or the oil pump. The first step in the manual is to check the oil level and add or drain oil as needed. Leave Standby OFF until the oil has been checked, so the engine does not restart low on oil. A GSHA technician checks it after making the unit safe. Call us and we will take it from there.

How do I reset a Cummins home standby generator after a fault?

First fix the simple cause, if there is one. On RS13A, RS14AF and RS20A/RS20AC panels, press BACK on the Fault screen to reset the fault. On the GSAA 12 kW, the manual does not describe a reset from the Fault screen, so check your operator manual or call us. Then press STANDBY ON/OFF, select ON with the arrow buttons and press BACK. The red STANDBY OFF lamp should go out and the display should say Standby ready enabled by user. For Low Oil Pressure (code 2), leave Standby OFF and call us instead. Only reset once. If the same fault returns, the problem needs a technician.

How often should a Cummins home standby generator be serviced?

Intervals vary by model, so check the operator manual for your unit. On the RS13A and the GSAA 12 kW, Cummins calls for an oil and oil filter change yearly or every 150 run hours. The RS14AF and RS20A/RS20AC schedule is tighter. Oil changes come as often as every 50 hours or once a season, and every 25 hours under heavy load or in high heat. The air filter, spark plugs, battery and cooling fins have their own intervals. Cummins also calls for a system test every three months. The exerciser can run the generator for 20 minutes every 28 days. Cummins notes that keeping up with maintenance greatly lowers the chance of a shutdown.

Related generator error code guides

Cummins® and Onan® are trademarks of Cummins Inc. GSHA Services, LTD is an independent contractor that installs, services and repairs Cummins home standby generators. This page is general guidance for homeowners; always follow the safety instructions in your owner’s manual and on the unit.