Generac Charger Warning (2770) and Charger Missing AC (2780): What They Mean

Your Generac air-cooled home standby generator is showing a yellow light. The display or the Mobile Link app says Charger Warning or Charger Missing AC. On the newest PowerZone 200 controllers these carry the codes 2770 and 2780. Both messages are about the battery charger built into the generator’s controller. This page explains what each one means, why it shows up, the few checks that are safe to do yourself, and when to call a Generac technician.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Battery, charger and transfer switch diagnostics
  • Serving Chicagoland & southeastern Wisconsin
In short: Charger Missing AC (2780) means the charger has no 120-volt power — for example on a new install that is not powered yet, or when a breaker is off. Charger Warning (2770) means the battery still read low after a full 18-hour charge. Both are warnings, so the generator can still run — check the breaker, clear the warning once, and call if it comes back.
Safety first. A generator in AUTO can start on its own at any time. Never remove a cover from the transfer switch or a panel from the generator, and never touch wiring. Even with the generator switched OFF, 120-volt power from the transfer switch is still present inside it. Leave that to a technician. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Exhaust contains carbon monoxide: never run a generator indoors or near a garage, and keep a working carbon monoxide alarm in your home.

What these warnings mean

Every Generac air-cooled home standby generator starts from a 12-volt battery, much like a car. The controller — the small computer under the lid — has a battery charger built in. It keeps that battery topped up between outages. The charger does not run off the battery. It runs off 120-volt house power that reaches the generator from the transfer switch (the box that moves your home between utility power and generator power). When something in that chain is not right, the controller shows one of these two warnings.

A note on the numbers: 2770 and 2780 are the E-codes used by the PowerZone 200 controller. Air-cooled Evolution controllers show only the words, so the numbers are here to help you match what the app or a Generac chart shows.

Charger Warning (2770)

The charger works in 18-hour cycles. A new cycle starts when the battery drifts a little below full, or whenever the engine cranks — the weekly exercise counts. At the end of the cycle the controller checks the battery. If it still reads low, the controller raises Charger Warning. In plain words: “I charged this battery for 18 hours and it still is not full.” On PowerZone 200 controllers the same warning also appears if the battery voltage runs too high. Charging then pauses until the problem is fixed.

Charger Missing AC (2780)

The charger has no AC power. The 120-volt supply that feeds it is not reaching the controller. The charger cannot run, so the battery is not being charged while the generator sits in standby.

For reference, from Generac’s service manuals: a charge cycle starts below about 12.6 volts (Evolution) or 12.7 volts (PowerZone 200). Charger Warning is set if the battery is under about 12.5 volts at the end of the cycle, and on PowerZone 200 also above 16.5 volts. Charger Missing AC is set after about 3 minutes without AC on PowerZone 200 and Evolution 2.0 controllers, and after about 15 seconds on Evolution 1.0.

Which Generac controllers show these warnings

  • Evolution 1.0 and 2.0 controllers were used on air-cooled units before the PowerZone line. They show the words Charger Warning or Charger Missing AC on the display and in the alarm log, and light the yellow LED. Generac’s Evolution service manual lists no 4-digit code for these two warnings.
  • PowerZone 200 (the newest air-cooled controller) uses the same names with E-codes 2770 and 2780. The owner’s manual says to check the app for details.
  • Older Nexus controllers do not use a number. At the end of a charge cycle they show the warning Inspect Battery instead of Charger Warning.
  • Liquid-cooled Generac units with Evolution controllers use the numbers 2770 and 2780 too, but the details vary by model. This page covers air-cooled units. If yours is liquid-cooled, check your owner’s manual or call us.

On current 10–28 kW units, the yellow “Non-Critical Alert” light on the side of the generator flashes once a second while a warning is active. It can be lit whatever state the generator is in. Both messages also appear in the app, which is the easiest place to read them without opening the lid.

Warning Yellow – still runs

A warning does not shut the generator down. It can still start and run during an outage. Both Charger Warning and Charger Missing AC are warnings.

Why it still matters

The battery is what starts the engine. If it keeps draining you may see Low Battery next, and then a generator that will not start when the power goes out. Not urgent like a red alarm — but do not leave it for weeks.

Why it happens

Charger Missing AC (2780) — most likely causes first

  1. The generator was just installed and the transfer switch is not powered yet. The charger is fed from the house side of the transfer switch through a small fuse inside the switch. While the generator waits in standby, that power comes from the utility. Until utility power reaches the switch and the breaker for it is on, the charger has nothing to run on. So this warning can show up on a brand-new unit.
  2. A breaker that is off or tripped. Generac’s service manual points out that the charger circuit depends on the transfer switch breaker. If that breaker is off, or no power is coming to it, the charger has no supply.
  3. A blown charger fuse in the transfer switch. The 120-volt feed passes through a small fuse in the transfer switch. If it blows, the charger loses power even though the house has power. A technician checks and replaces it, and looks for the reason it blew.
  4. A damaged or loose wire or connector between the transfer switch and the generator. The two small wires that carry this power run in the conduit (the pipe that carries the wires) from the switch to the generator. A damaged wire or a loose connector pin anywhere along that path can cut off the charger.
  5. A problem in the controller itself. If 120 volts reaches the controller’s charger input and Charger Missing AC stays on, Generac’s service procedures point to the controller.

During an outage the charger is briefly switched off until the generator has picked up the house load, so a short interruption during a transfer is normal.

Charger Warning (2770) — most likely causes first

  1. A battery near the end of its life. It takes a charge but cannot hold it. A battery that was left to run down for a long time can do the same — for example while a Charger Missing AC warning went unnoticed. The built-in charger is not meant to revive a dead battery. Generac says a battery that has run completely flat needs to be charged some other way before it goes back into service.
  2. Poor battery connections. Corroded or loose terminals and cables can keep the charge from reaching the battery, so it reads low at the end of the cycle.
  3. A problem in the charging path. A damaged pin or wire between the controller and the battery can keep the charge from getting through. On PowerZone units, a battery voltage that runs too high also sets this warning. A technician follows a set procedure to tell a battery fault from a charger-circuit fault.

What you can safely do

  1. Note the message. Open Mobile Link or look at the display and write down which of the two warnings you have and when it first appeared. Note whether Low Battery or Battery Problem is showing too. This tells our technician a lot before we arrive.
  2. If the generator was just installed, expect Charger Missing AC. It stays until the transfer switch is powered. Ask your installer (or us) where the start-up stands. Do not try to power up the switch yourself.
  3. Check the breakers with the generator in OFF. Press OFF on the generator first. Then look in your electrical panel for a breaker labeled for the generator or the transfer switch. Also look at any breaker on the transfer switch that you can see without removing a cover or using tools. If one is off or tripped, reset it once, then put the generator back in AUTO. If a breaker trips again, leave it off and call us. A fuse inside the switch also protects this circuit; only a technician checks that.
  4. Look, don’t take apart. Walk around the generator and along the conduit to the transfer switch and look for obvious damage. Do not remove any cover from the transfer switch or any panel from the generator.
  5. Clear it once and give the charger time. On Evolution controllers, press OFF, then ENTER, then AUTO. Generac’s Evolution owner’s manual says to contact a dealer if Charger Missing AC shows on the screen, so if it comes back, call. On PowerZone 200 controllers no button press is needed. Warnings there clear on their own once the cause is fixed. Charger Missing AC goes away when the charger has power again. Charger Warning goes away when the battery voltage is back to normal. The PowerZone owner’s manual says to check the app for details and contact a dealer for these warnings. On any controller, Charger Warning is only checked at the end of an 18-hour charge cycle, so allow a day before you judge. If a warning stays or comes back, stop there and call.
  6. Do not hook up a regular battery charger. Generac’s owner’s manual says not to use external battery chargers on these units. If the battery has run completely flat, the built-in charger cannot bring it back; a technician charges or replaces it. And do not leave the generator in OFF: put it back in AUTO so it is ready for the next outage.

What a GSHA technician checks

  • The battery and its cables first — voltage, condition, terminals and grounds. Generac’s test flow starts here for both warnings.
  • Whether 120 volts is actually reaching the charger input on the controller. If not, we trace it back through the generator’s connection block to the transfer switch to find where the voltage is lost.
  • The charger fuse and the breaker in the transfer switch. We also confirm the switch is in the correct position with voltage on both sides.
  • The wires between the switch and the generator for damage, loose pins or a bad connector.
  • The charger’s own output — that the controller reports “Charging” and that the correct charging voltage reaches the battery. That path runs through the starter contactor (the heavy relay that sends battery power to the starter), so its wiring is checked too.
  • The controller. If 120 volts reaches the controller and Charger Missing AC stays on, the controller is the next suspect. On PowerZone units, the power may be there and the warning gone while the battery still is not charging. Then we also test the charger that the engine drives while it runs, before deciding on the controller. We then confirm the warning clears and the next charge cycle completes. If the battery was disconnected during the repair, we also reset the exercise time and the clock.

When to call GSHA Services

  • The same warning comes back after you cleared it once, or it is still there after a full day.
  • You see Charger Missing AC on a generator that is not newly installed, and no breaker is off or tripped.
  • Charger Warning is joined by Low Battery or Battery Problem, or the battery has not been tested in a while.
  • The generator did not start during an outage, or the display went dark when it tried to start.
  • A breaker trips again after you reset it once.
  • Anything involving the transfer switch fuse, the wiring, or the controller — that is technician work.

As an authorized Generac dealer, GSHA Services tests batteries and chargers and traces the charger circuit through the transfer switch. We repair Generac home standby generators using Generac service procedures and genuine parts, including warranty repairs on qualifying units. A battery and charger check is part of every generator tune-up. Learn more about our generator repair service and Generac generator installation.

Request Generac service

Tell us which warning you see (Charger Warning 2770 or Charger Missing AC 2780) and whether the generator was recently installed. Add the model number if you have it — it is on the generator’s data label along with the serial number, and on your installation paperwork. Let us know the best time to reach you, and our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions

Is Charger Missing AC (2780) an emergency?

No. It is a warning, not a shutdown alarm. The generator can still start, but its battery is not being charged, so the warning should be fixed before the battery runs down. With the generator in OFF, check for a breaker that is off or tripped and reset it once. Then put the generator back in AUTO, and call for service if the warning returns.

Why does my new Generac generator say Charger Missing AC?

The battery charger inside the generator runs on 120-volt power that comes from the transfer switch. Until the transfer switch is powered and its breaker is on, the charger has no power, so the controller shows Charger Missing AC. Once the installation is finished and the switch is powered, the warning can be cleared. If it comes back, contact your installer or an authorized Generac dealer.

What is the difference between Charger Warning (2770) and Charger Missing AC (2780)?

Charger Missing AC means the charger has no AC power at all. Charger Warning means the charger had power and ran a full 18-hour charge cycle, but the battery still measured low afterward. That is often a battery that needs to be replaced, and sometimes a problem in the charger circuit.

Can I put a regular battery charger on my Generac generator?

No. Generac tells owners not to use external battery chargers on these units. If the battery has run down, have a technician test it and, if needed, charge or replace it.

Will Charger Warning clear on its own?

It can. On PowerZone 200 controllers, charger warnings clear on their own once the battery voltage is back to normal. That is checked again at the end of the next 18-hour charge cycle. On Evolution controllers, clear it once with OFF, then ENTER, then AUTO. If the warning is still there after a day, or it comes back, the battery or charger needs to be tested.