Generac Overcrank Alarm (Code 1100/1101): Generator Cranks but Won’t Start

Your Generac home standby generator tried to start and turned over several times. Then it stopped with a red light. The word “Overcrank” showed on the screen or in the Mobile Link® app, often with the number 1100 or 1101 next to it. This page explains what the alarm means, why it happens, the safe checks you can do yourself, and when it is time to call a Generac technician.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Serving Chicagoland & southeastern Wisconsin
In short: Overcrank means the engine turned over but never caught and ran, so the controller stopped cranking to protect the generator from damage. The first thing Generac has you check is the fuel supply — a closed gas valve or an empty propane tank. Check the fuel valve, clear the alarm once, and try one start in MANUAL. If it still will not start, or it starts and runs rough, leave it in OFF and call us.
Safety first. A generator set to AUTO can start on its own at any moment, so never reach inside the unit or remove panels. If you smell gas near the generator, do not press any buttons — leave the area and call your gas utility or 911 from a safe place. Generator exhaust contains carbon monoxide: never run a generator indoors or near open windows, and keep a working carbon monoxide alarm in your home.

What the Overcrank alarm means

When the power goes out, the controller (the small computer inside the generator) tells the engine to crank. That is the same thing a car engine does when it turns over before it starts. The controller makes a series of timed attempts with short rests in between. On Evolution controllers, Generac describes five attempts. If the engine never starts and runs on its own, the controller gives up, shuts everything down and shows Overcrank. On most units the code 1100 appears with it.

Overcrank is an alarm, not a warning. That matters. The red light is on, and the generator will not start by itself during an outage until the alarm is cleared. Your home is not protected while it sits this way.

One useful detail: Overcrank means the engine is turning. If your generator is silent or just clicks and never turns over, the controller usually shows a different alarm, often RPM Sensor Loss. In that case the battery or starter becomes the more likely suspect.

The alarm is a protection feature. Without it, a generator with no fuel would keep trying to start until something was damaged. Generac’s service manual is also clear on one point: if the cause is not fixed, Overcrank will come back the next time the generator tries to start.

Which Generac models show code 1100 or 1101

  • Evolution 1.0 and Evolution 2.0 controllers (units with a small screen): the display shows “Overcrank” with code 1100.
  • 8 kW and 9 kW units with the Evolution 1.0 controller can also show code 1101. It has the same meaning. The controller reaches it after ten unsuccessful crank attempts, and Generac labels it an engine or starter problem. It exists to limit cranking and protect the starter motor.
  • PowerZone 200 controllers are on the newest air-cooled units. They use LED lights and the Mobile Link app instead of a screen. On these units the alarm is code 1100, described as “engine cranks but will not start.” The unit flashes a red light, and the word Overcrank appears in the app.
  • Nexus controllers (older units): the screen shows “OVERCRANK” with no number.

If your generator is connected to Mobile Link®, the alarm also shows up in the app, and the app can notify you when an alarm occurs. On a unit with no screen, the app is the easiest place to read the alarm.

Why it happens (most likely causes first)

An engine needs four things to run: fuel, air, a spark, and compression. Compression is the squeeze inside the cylinder that lets the fuel burn and push the piston. The engine also has to be cranked fast enough to catch. Overcrank means something on that list was missing while the engine turned over. Here are the causes, most likely first.

1. No fuel, or not enough fuel

This is the first thing Generac has you check, and it is the example Generac gives for this alarm. The manuals say plainly that the engine will not start without an adequate gas supply and enough fuel pressure. Common reasons:

  • The gas shutoff valve on the line to the generator was closed. Generac’s owner’s manual makes checking this valve the first step for Overcrank.
  • The propane tank is empty or very low. The generator runs on the vapor that forms above the liquid in the tank. Generac says that vapor pressure must be high enough for the engine to run, and a nearly empty tank may not supply enough vapor pressure.
  • The natural gas supply is interrupted — for example, if the gas service to your house is off. Without a gas supply, the generator has no fuel either.
  • Fuel pressure is too low at the generator. The regulator is the small device on the gas line that sets the pressure going into the generator. It may have a problem, or the gas line may be too small. A technician measures this with a gauge.
  • The generator’s internal fuel type setting (natural gas vs. propane) does not match the fuel it is connected to.

Generac’s PowerZone service manual even notes that cranking a unit with the fuel turned off can produce code 1100. That is exactly what a closed valve looks like to the controller.

2. Battery or starter not turning the engine fast enough

The engine has to reach a set speed on the starter before the controller counts a start. A tired battery, corroded cables or a worn starter can turn the engine, but too slowly for it to catch. On 8 and 9 kW Evolution 1.0 units, code 1101 is Generac’s way of flagging an engine or starter problem.

3. No spark

Worn spark plugs, a failed ignition coil or a wiring problem in the ignition circuit will let the engine crank normally but never fire. Generac lists an ignition failure as one of the causes when an engine cranks but does not start.

4. Blocked air

A clogged or wet air filter, or a blocked air intake, starves the engine. Checking the air filter is the first step in Generac’s cranks-but-won’t-start procedure.

5. Fuel or throttle parts inside the generator

The fuel shutoff valve inside the unit (the fuel solenoid) may not be opening. Or the small motor that controls the throttle and mixer may be stuck. These need testing with the panels off.

6. Engine or controller problems

Less often, the cause is inside the engine, such as valve adjustment or low compression. It can also be in the controller or its wiring to the fuel solenoid and ignition. These are technician items.

What you can safely do

Everything below can be done from outside the enclosure or at the control panel. Do not remove any panels, and stop if you smell gas.

  1. Write down the alarm and code, or take a photo of the screen or the Mobile Link app. Note whether it has happened before. This helps us arrive with the right parts.
  2. Check the fuel supply. Generac’s owner’s manual lists this as the first thing to check for Overcrank. Make sure the gas shutoff valve on the line to the generator is open (ON). If you have propane, look at the tank gauge. If your natural gas supply is off — for example, during a utility gas outage — the generator has no fuel until it is restored. Do not touch the regulator, the gas piping or anything inside the unit.
  3. Look and listen around the outside. Clear snow, leaves, grass clippings or nests away from the air intake and exhaust openings. If you smell gas at any point, stop here, leave the area and call your gas utility.
  4. Clear the alarm — once. On Evolution units with a screen, press OFF and then ENTER. Some owner’s manuals add a press of AUTO after that, and some describe pressing ENTER twice and then AUTO. Follow the clear-alarm steps in your owner’s manual. On the newest units with LED lights and no screen, press and hold OFF for at least three seconds until the red OFF light stops flashing and stays solid. On older Nexus units, follow the steps in your owner’s manual.
  5. Try one start in MANUAL. This is what Generac’s owner’s manual tells owners to do after checking the fuel valve. Press MANUAL and listen. If the engine starts and runs smoothly, press OFF, then press AUTO so it is ready for the next outage. If it does not start, or it starts but runs rough, press OFF and call us. Do not keep trying — repeated cranking is exactly what this alarm is designed to prevent.
  6. Return the unit to AUTO only if it ran normally. A generator left in OFF will not protect your home. If it started this time but the cause was not obvious, book a service visit anyway so it does not fail during a storm.
Remember: clear the alarm one time. If Overcrank comes back, there is a real problem that resetting will not fix, and each extra crank cycle adds wear to the starter.

What a GSHA technician checks

Our technicians follow Generac’s cranks-but-will-not-start procedure. Without going into test numbers, here is what that visit looks like:

  • Fuel supply and pressure — measured with a gauge at the generator, both at rest and while cranking. We also check the regulator, the fuel solenoid and the fuel type setting, and whether the gas line is sized correctly for your unit.
  • Battery, cables and starter — battery voltage and condition, cable connections, and whether the engine reaches proper cranking speed.
  • Ignition — spark at the plugs, spark plug condition and gap, and the ignition coils.
  • Air — the air filter and intake path for dirt, water or obstructions.
  • Throttle and mixer — the stepper motor that controls engine speed and the air/fuel mixer, which can stick or fail.
  • Engine and controls — valve adjustment and compression if the basics check out. We also check the controller firmware and the wiring between the controller, fuel solenoid and ignition.

When the cause is inside the unit, we repair it with genuine Generac parts, clear the alarm, test-run the generator and put it back in AUTO before we leave.

When to call GSHA Services

  • The Overcrank alarm came back after you cleared it once.
  • The generator did not start in MANUAL, or it started but ran rough or shut down again.
  • The gas valve was open and the propane tank had fuel, but it still would not start.
  • The generator does not crank at all — that is a different problem, and it still means your home is unprotected.
  • You smell gas (call your gas utility first), see smoke, or hear grinding or clicking while it cranks.
  • It has been more than a year since the generator was serviced. Old spark plugs, a weak battery and a dirty air filter are all Overcrank causes that annual maintenance catches early.

As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators using Generac service procedures and genuine parts. Learn more about our generator repair service or, for an older unit with repeated no-start problems, our Generac generator installation options.

Request Generac service

Tell us the alarm you see (Overcrank, 1100 or 1101) and your generator’s fuel type. Add the model from the data plate if you have it, and the best time to reach you. Our team will contact you to schedule a visit. If you are in the middle of an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions

What does Generac error code 1100 mean?

Code 1100 is the Overcrank alarm. The generator cranked through its full set of start attempts, but the engine never started and ran, so the controller shut down to protect the generator from damage. The first thing Generac has you check is the fuel supply: a closed gas valve or an empty propane tank. The generator will not start on its own during an outage until the alarm is cleared and the cause is fixed.

What is the difference between Generac codes 1100 and 1101?

Both mean Overcrank. Code 1100 appears on Evolution and PowerZone 200 controllers after the normal set of crank attempts. Code 1101 only appears on 8 kW and 9 kW units with the Evolution 1.0 controller, after ten unsuccessful attempts. Generac labels 1101 an engine or starter problem. Older Nexus units show the word OVERCRANK with no number.

Can I reset a Generac Overcrank alarm myself?

Yes, once. Check that the gas valve to the generator is open and the propane tank has fuel. Then clear the alarm. On Evolution units press OFF and then ENTER (your owner’s manual may add a press of AUTO). On the newest units with LED lights, hold OFF for at least three seconds until the red light stays solid. Try one start in MANUAL. If it starts and runs smoothly, press OFF and then AUTO. If it does not start or runs rough, leave it in OFF and call a Generac technician.

Why does my Generac keep showing Overcrank after I reset it?

Because the alarm is a symptom, not the problem. If the engine still has no fuel, no spark, blocked air or too little cranking speed, it will fail to start again and the controller will show Overcrank again. Generac’s service manual says the alarm will continue to occur until the cause is repaired. Repeated resets only add wear to the starter, so stop after one try and call for service.

My generator does not crank at all. Is that the Overcrank alarm?

Usually not. Overcrank means the engine was turning over but would not start. If the engine is silent or just clicks, the controller typically shows a different alarm, often RPM Sensor Loss. A weak battery, a bad starter or a wiring problem is then the more likely cause. Either way the generator will not protect your home, so it needs a technician.