Generac Generator Won’t Start During an Outage: What to Check First
The power is out, the house is dark, and the Generac in the yard is quiet. Before you assume something is broken, know that most no-start calls we get come down to a handful of simple things. Many of them show no error code at all. Here is what to look at first, what is safe to do yourself, and when it is time to call.
- Authorized Generac dealer
- Generac-trained technicians
- Serving Chicagoland & southeastern Wisconsin
What is the light on a quiet Generac telling you?
Current Generac air-cooled models have status lights on the outside of the enclosure, so you can check them without opening anything. On older Evolution and Nexus units the lights and screen are on the control panel under the lid. Alarms and warnings also show up in the Mobile Link app. On current models:
Solid red
The generator is set to OFF. It will not start on its own in this mode.
Flashing red
An alarm has stopped the unit, or the emergency shutdown switch on the outside of the enclosure was pressed. The app will name the alarm.
Solid green
The unit is in AUTO and ready. If the power is out and it still does not start, call us. A technician may need to check a start setting called two-wire start.
Flashing green, slow
The unit is in AUTO and is counting down before it cranks. A short delay after the power drops is normal. Stay clear of the unit and give it a moment.
Yellow (with any other color)
Flashing yellow means a warning such as Low Battery is active, or maintenance is due. Solid yellow means the unit is running in MANUAL. A warning alone does not stop the unit, but a weak battery can.
Older Nexus units show the alarm name on a small screen under the lid. Evolution controllers (the generator’s control board) show the name plus a four-digit code on their screen. On current models with the PowerZone controller, check the Mobile Link app for the alarm; a technician reads the full code with Generac’s service app. Your owner’s manual has the full light chart for your model — see also our guide to what the Generac lights mean.
Why won’t my Generac start when there is no error code?
1. The unit was left in OFF
The OFF button shuts the engine down and blocks automatic operation. If someone pressed OFF after a service visit, a noisy exercise, or a false alarm, the generator will sit quietly through an outage. The light is solid red. The scheduled exercise also runs only in AUTO. If the unit has missed its scheduled exercise, check the mode and look in the app for an alarm.
2. The emergency shutdown switch was pressed
Current models have an emergency shutdown switch on the outside of the side panel. It stops the generator and blocks restarts until it is reset. When it is active, the red light flashes and the Mobile Link app says the generator was stopped by the emergency shutdown switch. Generac says not to use it as the everyday off switch, because that can damage the unit. Evolution controllers log it as Shutdown Switch (code 2800). On current PowerZone models, code 2800 is Emergency Shutdown Pressed. Code 2801 (Auxiliary Shutdown) points to an optional remote shutdown switch instead. Some older Evolution units of 15 kW and up also have a second shutdown switch inside the enclosure; a technician checks that one.
3. The gas valve is closed or the propane tank is empty
A generator needs a steady gas supply to start. If the shutoff valve on the pipe feeding the generator is closed, the engine will crank but never catch. Propane generators run on the vapor that forms above the liquid in the tank. If the tank runs empty or very low, the engine cannot get the fuel it needs. If the engine cranks through its full crank cycle without catching, the controller stops and logs Overcrank (code 1100). Generac’s first troubleshooting step for Overcrank is to make sure the fuel line shutoff valve is on.
One important exception: if your gas utility, your propane supplier or a technician closed that valve, or you do not know why it is closed, do not reopen it. It may have been closed for a safety reason. Call them, or call us. On propane, your part is to read the tank gauge and call your supplier if it is low. Gas pressure and the regulator are technician items.
4. The battery is dead — Low Battery, Battery Problem, No Rotation Warning
The controller watches battery voltage and posts a Low Battery warning (yellow) when it stays below about 12.1 volts for a minute. On PowerZone controllers a much deeper discharge becomes a Very Low Battery alarm. A Battery Problem warning comes at the end of an 18-hour charge cycle. It means the battery was still drawing heavy charge current, or its voltage read too high. Either way, the battery should be tested. Charger Missing AC means the built-in charger has lost its 120-volt supply, so the battery is not being charged. That supply comes through a fuse in the transfer switch, the box near your electrical panel that moves the house from utility power to generator power. A technician checks that fuse. Our pages on Battery Problem and Low Battery and Charger Warning and Charger Missing AC explain each message.
When a weak battery or a starter problem keeps the engine from turning over at all, Evolution controllers log RPM Sense Loss or a No Rotation Warning. Generac’s service manual notes that a common cause of an RPM sense fault is that the engine never cranked. That can be a weak battery, a faulty starter, or a fault in the crank circuit. On current models, Generac’s chart says to check the battery condition in the app when RPM Sense Loss keeps the unit from starting.
One more case is a blown 7.5-amp fuse in the control panel. Generac lists it as a cause of an engine that will not crank. On Evolution controllers, a blown fuse has the same result as setting the unit to OFF. During an outage in AUTO, the controller may simply go dark with no alarm or warning logged. A technician checks the fuse and finds out why it blew. Older Evolution firmware showed this as Fuse Problem (2400).
5. The generator runs, but the house has no power
The generator has its own main breaker, which Generac calls the main line circuit breaker or generator disconnect. If it is left OFF, the unit will start and run during an outage but send no power to the house. Also give the unit its warm-up time. On a cold day, Cold Smart Start (if enabled) holds the transfer for about 30 seconds so the engine can warm up before it takes the load.
6. The transfer switch did not transfer
The transfer switch is the box near your electrical panel that moves the house from utility power to generator power. If the generator runs but the switch does not move, the cause can be the switch’s coil, its relay or relay circuit, or the controller. PowerZone controllers log this as a No Transfer Detected warning (code 2738). Mis-wired or crossed control wires between the generator and the switch show as Wiring Error (2098/2099). All of these are technician items. The switch has live utility power inside, so please do not open it.
7. An alarm from earlier is still active
Many shutdown alarms stay active until someone clears them. Say the generator shut down last week on Low Oil Pressure (1300), Overcrank, RPM Sense Loss or Overload Remove Load, and nobody cleared it. With one of these alarms active, Generac’s charts say the unit will not start in AUTO when the next outage hits. The light flashes red. Check the app or the screen for the alarm name and look it up on our Generac error code list. Fix the simple cause if there is one, and clear it once.
8. The unit was never activated
A new generator has to be registered and configured before it can be placed in AUTO. If yours was installed recently and the screen says NOT ACTIVATED, or the unit will not go into AUTO after a new installation, the setup was never finished. Call the installer, or call us and we can complete it.
What you can safely do, step by step
- Note the light and any message. Check Mobile Link and write down the alarm name and code, if any. A photo of the app or screen helps us bring the right parts. If the light is flashing green, the unit is counting down to start: stay clear and give it time. The rest of these steps are for a unit that is not trying to start.
- Put the unit in OFF before you check anything. Lift the lid and press OFF (older Nexus units have an AUTO/OFF/MANUAL switch instead). On older units, write down what the screen says. Leave it in OFF until step 7. In AUTO, it can crank on its own within seconds during an outage. If the light was already solid red with no alarm, the unit was simply left in OFF. Do the quick checks below, then press AUTO in step 7.
- Check the emergency shutdown switch on the outside of the enclosure. If it was pressed, set it back to the closed (I) position. You will clear the alarm in step 7. If someone pressed it because of smoke, a strange noise or a gas smell, or you do not know why it was pressed, leave it and call.
- Check the gas. Look at the shutoff valve on the gas line to the generator. If it is closed and you closed it yourself, you can open it. If the gas utility, your propane supplier or a technician closed it, or you do not know why it is closed, leave it closed and call. On propane, read the tank gauge and call your supplier if it is low. If you smell gas at any point, stop, leave, and call the gas utility.
- Check the generator’s own breaker. With the unit still in OFF, look under the generator lid and confirm the generator’s main breaker (the generator disconnect) is ON. Do not open any other covers.
- Look around the unit. With the unit still in OFF, clear snow, leaves, grass clippings and nests from the intake and exhaust sides so air can flow.
- Clear the alarm once, then press AUTO last. On current models, press and hold OFF for at least three seconds; the red light turns solid when the alarm clears. On Evolution and Nexus units, with the controller in OFF, press ENTER on the keypad. If no alarm was showing, skip straight to AUTO. Press AUTO, close the lid and step away. If the power is still out, the generator may crank and start within seconds.
- If the same alarm comes back, stop. Do not keep resetting. Generac’s own guidance is to contact a certified dealer when an alarm reoccurs — call us.
What a GSHA technician checks
- The controller’s 7.5-amp fuse, the charger fuse in the transfer switch, the battery’s voltage and cable connections, and the built-in charger’s output.
- The crank circuit: starter control relay, starter contactor and starter motor, if the engine does not turn over.
- Gas supply pressure at the regulator, the fuel selector setting (natural gas vs. propane) and the fuel solenoid, if the engine cranks but will not start.
- Air filter, spark and spark plugs, and the ignition magnetos.
- Transfer switch control wiring, the utility-sensing settings (start delay, two-wire start) and the transfer relay.
- Controller activation and the alarm history.
When to call GSHA Services
- The generator is in AUTO with gas available and still will not crank or will not start.
- The same alarm returns after you cleared it once.
- The gas valve was closed by the utility, your propane supplier or a technician, or you do not know why it is closed.
- You see Low Battery, Battery Problem, Charger Warning or Charger Missing AC — these point to the battery or its charger and should be tested before the next outage.
- The generator runs but the house has no power and the generator’s main breaker is on.
- The screen or controller is dark, or the unit says NOT ACTIVATED.
- You smell gas, hear unusual noises, or see smoke.
- It has been more than a year since the last service. A tune-up catches weak batteries and fuel problems before an outage does.
As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators and automatic transfer switches using Generac service procedures and genuine parts. We handle warranty repairs on qualifying units and perform annual maintenance so the generator is ready when the lights go out. Learn more about our generator repair, generator tune-up and Generac generator installation services.
Request Generac service
Tell us what the light is doing, any alarm name or code from the app, your generator model (from the data plate if you have it) and the best time to reach you. For an urgent problem during an outage, please call (224) 220-3660.
Generac service area
GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.
Related Generac codes and guides
Frequently asked questions
Why didn’t my Generac generator turn on when the power went out?
The most common reasons show no error code. The unit was left in OFF, the emergency shutdown switch was pressed, the gas valve is closed or the propane tank is low, or the battery is too weak to crank the engine. Check the light and the Mobile Link app first. Put the unit in OFF while you check it, and press AUTO last. If an alarm is showing, clear it only once. If it still will not start, call a Generac technician.
What does a solid red light on a Generac generator mean?
On current Generac air-cooled models a solid red light means the controller is in OFF, so the generator will not start on its own. A flashing red light means an alarm is active or the emergency shutdown switch was pressed. Once your checks are done, press AUTO to put the unit back into automatic mode. Then close the lid and step away. During an outage it may start within seconds. If the red light flashes, check the app for the alarm name.
How do I reset a Generac generator that won’t start?
Fix the simple cause first, such as resetting the emergency shutdown switch. Then clear the alarm once. On current models, press and hold OFF for at least three seconds until the red light turns solid. On Evolution and Nexus units, set the controller to OFF and press ENTER. Then press AUTO, close the lid and step away. If the power is out, it may start within seconds. If the same alarm comes back, the generator needs a technician.
Can a dead battery keep a Generac from starting?
Yes. A weak battery is one of the common no-start causes we see. The controller shows a Low Battery warning when voltage stays low, and a Battery Problem warning when the battery fails its charge cycle. If the engine does not turn over at all, Evolution controllers log RPM Sense Loss or a No Rotation Warning. The built-in charger is not designed to bring back a fully dead battery, so the battery needs to be tested and then recharged or replaced.
My Generac is running but my house still has no power. Why?
On a cold day, give it about 30 seconds first. Cold Smart Start may be warming the engine. After that, either the generator’s own main breaker (the generator disconnect under the lid) is off, or the transfer switch did not move the house over to generator power. Put the unit in OFF and check the generator breaker. If it is on, the transfer switch or its control wiring needs a technician; do not open the transfer switch yourself.
Generac® and Mobile Link® are trademarks of Generac Power Systems, Inc. GSHA Services, LTD is an authorized Generac dealer. This page is general guidance for homeowners; always follow the safety instructions in your owner’s manual and on the unit.