Generac Generator Red, Yellow and Green Lights: What They Mean

Your Generac home standby generator has a small cluster of status lights on the outside of the enclosure. When one turns red, a yellow light starts blinking, or the green light changes from steady to flashing, the generator is telling you what it is doing. This page explains each light and each flash pattern in plain words, what is safe for you to do, and when it is time to call a Generac technician.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Serving Chicagoland & southeastern Wisconsin
In short: On current Generac models with four lights (PowerZone 200), solid green means AUTO and ready, and flashing green means it is about to start (every 2 seconds) or is powering your home (every second). Solid red means OFF and flashing red means an alarm; solid yellow means it is running in MANUAL and flashing yellow means a warning or maintenance reminder. On older three-light Evolution units, a solid red light can mean OFF or an alarm, so check the display under the lid or the app first.
Safety first. A generator in AUTO can start on its own at any time. Open only the lid to press the control buttons or check the generator breaker. Never remove panels, reach into the engine area, or touch wiring, and keep your hands clear of the engine and fan whenever it is running. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Exhaust contains carbon monoxide: never run a generator indoors or near a garage or open window, and keep a working carbon monoxide alarm in your home.

Which Generac lights does this page cover?

Current Generac air-cooled home standby models (10 to 28 kW) have four lights behind a small lens on the side panel: green, yellow, red and blue. Generac’s current owner’s manual has a full chart of their patterns. Generac’s service manual shows the same chart for its newest controller, the PowerZone 200. The controller is the generator’s built-in computer and button panel, under the lid. On this page, “four-light models” means these units.

Earlier units with the Evolution controller have three lights in a similar lens on the side panel, next to the lock: green, red and yellow. There is no blue light in that cluster, and the colors do not mean quite the same thing. The biggest difference: on an Evolution unit, a solid red light can mean OFF or an alarm. Each section below has a short “On Evolution units” note. Older Nexus units vary — check your owner’s manual.

Four-light models also have a second set of lights on the controller itself, under the lid. They show which mode button is selected: green for AUTO, red for OFF, yellow for MANUAL and blue for SERVICE. The lights on the outside of the enclosure are the ones most homeowners see, so they are the focus here.

Green light: ready, counting down, or running

On four-light models:

Solid green

The generator is in AUTO and utility power is present. This is the normal, everyday look. Solid green can also show while the engine runs in AUTO but has not yet moved your house onto generator power. One example is the short warm-up before it takes over in an outage.

Flashing green, every 2 seconds

Utility power has dropped and the generator is in its short delay before cranking. The factory delay is about five seconds, and a dealer can change it. If the slow flash goes on much longer than that and the engine never starts, note it and call us.

Flashing green, every second

The generator is running and powering your home. The transfer switch — the box that moves your house between utility power and generator power — has switched over. This is normal during an outage. If you see this pattern but the house has no power, open the lid and look at the generator’s main breaker (the “generator disconnect”). The engine is running, so keep your hands clear of the engine and fan. If the breaker is OFF, switch it ON once. If it is already ON, or it switches off again, call us.

On Evolution units: solid green means the generator is in AUTO and ready to take over if the power goes out. On Evolution 2.0 units, and 2017-and-newer Evolution 1.0 units with firmware 1.17 or higher, the green light flashes once the generator has taken over and is powering your home. Generac’s manuals for these units do not describe separate 1-second and 2-second flash patterns.

Red light: OFF or alarm

On four-light models:

Solid red

The generator is in OFF. It will not start on its own during an outage and it will not run its scheduled exercise. If nobody meant to leave it off, open the lid and press AUTO. The engine may start when you do.

Flashing red (about once a second)

A fault has been detected. The generator has shut down, or will not start, until the alarm is cleared. The alarm name (for example High Temperature, Low Oil Pressure, Overcrank or Overload) shows in the Mobile Link app. A flashing red light can also mean the emergency shutdown switch on the side of the unit was used. On homes with a remote emergency stop switch, it can mean that switch was activated.

What you can do about a flashing red light (four-light models): open Mobile Link and read the alarm name. Fix the simple cause if there is one. For High Temperature, clear leaves or snow from the vents. For Overcrank, make sure the shutoff valve on the gas line outside the unit is open. For Overload, turn off large appliances. Then open the lid, and press and hold OFF for at least three seconds. The red light stops flashing and turns solid when the alarm has cleared. Press AUTO to put the generator back in service.

If the emergency shutdown switch on the side of the unit was used, set it back to CLOSED (I) first, then hold OFF for three seconds. If a remote emergency stop switch was used, reset that switch first. Clear the alarm only once. If the red light flashes again, stop and call a Generac technician. Our Generac error code list explains each alarm.

On Evolution units: the red light is on both when the generator is in OFF and when an alarm has stopped it. Generac’s manuals for these units do not list a separate flashing pattern for an alarm. So before you press anything, read the message on the controller display under the lid, or in Mobile Link if your unit is connected. To clear an alarm once, press OFF, then ENTER, then press AUTO. If the alarm comes back, call us. If the unit was only left in OFF and missed a scheduled exercise, it will try to run that exercise as soon as you press AUTO.

Yellow light: MANUAL, warning or maintenance

On four-light models:

Solid yellow

The generator is running in MANUAL. Someone pressed the MANUAL button, so the engine runs but the house stays on utility power unless utility fails. When you are done, open the lid and press OFF to stop the engine, then AUTO so the generator is ready for the next outage.

Flashing yellow (about once a second)

A warning is active or maintenance is due. A warning is a condition that should be looked at but does not shut the generator down. Common ones are Low Battery, Battery Problem, Charger Warning and Charger Missing AC. Maintenance reminders are Service A, Service B, Service C and Inspect Battery.

The yellow light can be lit at the same time as the green or red light. So “solid green plus flashing yellow” simply means the unit is in AUTO and has a warning. Check Mobile Link to see which one. For a Low Battery warning, check the battery condition in the app, then call us. For a Battery Problem or any charger warning, call us. For maintenance reminders, book a generator tune-up. The reminder is cleared with “Clear Maintenance” in the app after the work is done.

On Evolution units: yellow is a maintenance or warning alert. It does not mean the unit is running in MANUAL. Read the controller display or the app to see which alert it is.

Blue light: service mode

On four-light models, a solid blue light means the SERVICE button on the controller was pressed, usually by a technician. Service mode pauses Mobile Link notifications and blocks remote start and stop commands. That lets a technician work on the unit without alerts going out. It also blocks remote firmware updates. The blue light can be on together with any other color, because the generator can be in AUTO, OFF or MANUAL at the same time as SERVICE. It should go off when the technician is finished. If the blue light is still on after a service visit, call us — you will not receive app notifications while it stays on. Evolution units have no blue light in the outside light cluster.

Two lights at once: the full chart in plain words

Here is the complete light chart from the current Generac owner’s manual for four-light (PowerZone 200) models, translated into everyday language. For any row with an alarm, follow the red-light steps above.

Lights you seeGenerator stateWhat it means and what you can do
Solid greenAUTO, ready (or running in AUTO before it takes over the house)Normal. Nothing to do.
Flashing green, 2-secondAUTO, utility lost, delay countdownPower dropped; the generator is about to crank. If it never starts, call.
Flashing green, 1-secondRunning in AUTO, home transferredNormal during an outage. No power inside? Check the generator main breaker (hands clear of the running engine), then call.
Solid green + flashing redAUTO with an alarmThe unit will not start in an outage. Read the alarm in the app and clear it once using the red-light steps. If it returns, call.
Solid green + flashing yellowAUTO with a warning or maintenance dueStill ready to run. Check the app and schedule service soon.
Solid redOFFNot protected. Press AUTO.
Flashing redOFF with an alarm, or an emergency shutdown switch was usedRead the alarm. Reset the shutdown switch if it was used. Clear once using the red-light steps. If it returns, call.
Solid red + flashing yellowOFF with a warning or maintenance dueCheck the app, then press AUTO so you are protected while service is arranged.
Solid yellowRunning in MANUALPress OFF, then AUTO when you are done.
Flashing yellowRunning in MANUAL with a warning or maintenance dueCheck the app. Press OFF, then AUTO. Schedule service.
Flashing red + solid yellowMANUAL with an alarmRead the alarm and clear it once using the red-light steps. If it returns, call.
Flashing green (1-sec) + solid yellowRunning in MANUAL, home transferredUtility failed while the unit was in MANUAL. When power is back, press OFF, then AUTO.
Solid blue + any other colorSERVICE modeA technician mode. App notifications are paused. Call if it stays on.
All four, circling counterclockwiseMain controller software (firmware) update in progressOur advice: leave it alone until it finishes. See below.
All four, circling clockwiseEngine computer (ECM) software update in progressOur advice: leave it alone until it finishes. See below.

Chart applies to current Generac air-cooled home standby generators with four lights (PowerZone 200 controller). Evolution and Nexus units use fewer lights and different patterns — on Evolution units, red can mean OFF or an alarm. Your owner’s manual has the chart for your unit.

All four lights flashing in a circle: a firmware update

Current four-light Generac units come with a connectivity accessory. It links the generator to Generac’s servers over cellular or Wi-Fi. Besides feeding the Mobile Link app, it can receive remote firmware updates — software updates for the generator’s computers. While an update is loading, all four lights chase around in a circle:

  • Counterclockwise (red, green, yellow, blue): the main controller is being updated.
  • Clockwise (red, blue, yellow, green): the engine control module (ECM), the small computer that runs the engine, is being updated.

Generac’s manual names these two patterns but gives no homeowner steps for them. Our advice is simple: leave the generator alone until the lights go back to a normal pattern. If an alarm shows up right after an update, clear it once (hold OFF for 3 seconds, then press AUTO). If it comes back, call us.

Two more points. A unit in SERVICE mode (blue light) will not take remote updates. And some alarms cannot be cleared remotely; those must be fixed before the controller will accept an update.

What you can safely do

  1. Note the light pattern — which colors, solid or flashing, and how fast. Take a photo if you can. Then read the alarm or warning name in Mobile Link (our Mobile Link alerts guide explains the messages). On an Evolution unit, the name also shows on the controller display under the lid.
  2. Look around the outside of the unit. Are leaves, snow or grass blocking the vents? Is the shutoff valve on the gas line outside the unit open, and is the propane tank full enough? Was the emergency shutdown switch on the side of the unit used? Do not remove panels to look for the valve inside the generator.
  3. Solid red on a four-light model: open the lid and press AUTO. The engine may start. On an Evolution unit, solid red can also mean an alarm, so read the display first. If an Evolution unit missed a scheduled exercise while it was OFF, it will try to run that exercise as soon as you press AUTO.
  4. Solid yellow on a four-light model: press OFF, then AUTO.
  5. Flashing red on a four-light model: fix the simple cause, then hold OFF for at least three seconds until the red light turns solid, and press AUTO. On an Evolution unit: press OFF, then ENTER, then AUTO. Do this once only.
  6. Flashing yellow: check the app and book service. A weak battery can keep the generator from starting, so do not put off battery or charger warnings.
  7. Anything that repeats, or any light you cannot explain: leave the unit in AUTO if it will stay there, and call us.

Leave panels, fuses, wiring, gas pressure, the transfer switch and firmware to a technician.

What a GSHA technician checks

  • Reads the alarm and warning history from the controller with Generac’s Field Pro app over Bluetooth, so we know what happened and when.
  • Tests the battery and the built-in charger, including whether the charger is getting its 120-volt supply.
  • Reviews controller settings such as the start delay and the two-wire start setting. Two-wire start is an optional setup where a separate signal tells the generator when to start, instead of the generator watching utility power itself. A wrong setting can explain a green light with a generator that never starts.
  • Checks the generator main breaker and the transfer switch when the light says “running and transferred” but the house has no power.
  • Confirms the controller, the engine control module and the connectivity accessory are on current firmware and talking to each other, and that the controller can see the outside light module.
  • Clears maintenance reminders after service and puts the unit back in AUTO, out of SERVICE mode.

When to call GSHA Services

  • A flashing red light comes back after you cleared it once, or an Evolution alarm message returns.
  • A flashing yellow battery or charger warning does not go away.
  • The green light is flashing but your home has no power, or it flashes slowly and the engine never starts (see why a Generac won’t start).
  • The blue light stays on after a service visit.
  • No lights are lit at all. That is not one of the normal patterns.
  • You hear unusual noises from the unit.

If you smell gas or see smoke or fire, leave the area and call your gas utility or 911 first. Then call us.

As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators and transfer switches using Generac service procedures and genuine parts. We handle warranty repairs on qualifying units. We also perform annual maintenance so a flashing light does not surprise you during the next storm. Learn more about our generator repair, generator maintenance and Generac generator installation services.

Request Generac service

Tell us which lights you see, the alarm or warning shown in Mobile Link or on the controller display, your generator model if you have it, and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions about Generac lights

Why is the green light on my Generac generator flashing?

On current Generac models with four lights (PowerZone 200), a green light that flashes every 2 seconds means utility power dropped. The generator is in its short delay before it starts. A green light that flashes every second means the generator is running and your home has been switched over to generator power. Both are normal during an outage. If it flashes every second but the house has no power, open the lid and check the generator main breaker. Keep your hands clear of the running engine and fan, and then call for service. On Evolution units with newer firmware, a flashing green light means the generator has taken over and is powering your home.

What does a red light on a Generac generator mean?

On current Generac models with four lights (PowerZone 200), solid red means the generator is in OFF. It will not start during an outage or run its scheduled exercise until someone presses AUTO. Flashing red means a fault has stopped the generator, or an emergency shutdown switch was used. Read the alarm name in Mobile Link and fix the simple cause if there is one. Then open the lid, press and hold OFF for at least three seconds until the light turns solid, and press AUTO. On Evolution units with three lights, a solid red light can mean OFF or an alarm, so check the controller display or the app first. To clear an alarm on an Evolution unit, press OFF, then ENTER, then AUTO. Clear an alarm only once. If it comes back, call a Generac technician.

What does the yellow light on a Generac generator mean?

On current Generac models with four lights (PowerZone 200), a solid yellow light means the generator is running in MANUAL. A flashing yellow light means a warning is active, such as a battery or charger warning, or maintenance is due. Warnings do not shut the generator down, but have them looked at soon so the unit is ready for the next outage. On Evolution units, yellow is a maintenance or warning alert and does not mean MANUAL.

What does the blue light on a Generac generator mean?

On current Generac models with four lights (PowerZone 200), blue means the SERVICE button was pressed. Service mode pauses Mobile Link notifications and blocks remote commands while a technician works on the unit. It should be off when service is finished. If it stays on, call so we can take the generator out of service mode. Evolution units do not have a blue light in the outside light cluster.

Why are all four lights on my Generac flashing in a circle?

On current Generac models with four lights (PowerZone 200), all four lights chasing in a circle means a firmware (software) update is loading. Counterclockwise is the main controller; clockwise is the engine control module. Our advice is to leave the generator alone until the lights go back to a normal pattern. If an alarm shows right after the update, clear it once by holding OFF for 3 seconds and then pressing AUTO. If it comes back, call.