Generac Overload Remove Load Alarm (Codes 2100–2103, 2299): What It Means

Your Generac home standby generator shut down with a red alarm light. The screen or the Mobile Link app shows “Overload Remove Load” (code 2100, 2102 or 2103) or “Undervoltage Overload” (code 2299). Here is what the controller is telling you and what you can safely turn off and reset yourself. We also explain when the real fix is load management or a larger generator.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Load management and generator sizing for Generac home standby units
  • Serving Chicagoland & southeastern Wisconsin
In short: an overload alarm means your house asked the generator for more power than it is rated to supply, so the controller shut it down to protect it. Turn off the big appliances, clear the alarm once and put the unit back in AUTO. If it comes back, call a Generac technician; the fix is usually load management, a repair to the load-shedding equipment, or a larger generator.
Safety first. Never open the generator or touch wiring while it is running or set to AUTO — it can start on its own at any time. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Never run a generator in or near a garage or open window, and keep a working carbon monoxide alarm in your home.

What this alarm means

Every Generac home standby generator has a rated output — the most power it can supply without harm. The controller (the small computer under the lid) watches the load going out to your house. If the load stays above the rating, it stops the engine. A red alarm light comes on. On current PowerZone 200 units the red light flashes. On Evolution units the red light comes on and the screen backlight flashes. The screen (on units that have one) or the Mobile Link app shows the alarm name and a four-digit code. Until the alarm is cleared, the generator will not start for an outage.

Code 2100 — Overload Remove Load

On Evolution 1.0 and 2.0 controllers, two current sensors (one per output leg) measure the power leaving the generator. When one or both sees more current than the unit is rated for, the controller logs 2100 and shuts down. Generac’s service notes point at two fixes. Change what is connected, or use load shedding at the transfer switch — the box that moves your house between utility and generator power.

On the newest PowerZone 200 controller (current 10–28 kW units) the alarm has the same name and number. The controller senses the overload a different way. How long it waits before shutting down depends on how far past normal the generator is being pushed. PowerZone units also have a close cousin, 2115 “AVR PWM Overload,” set when the voltage regulator itself senses the overload.

Codes 2102 and 2103 — 8 and 9 kW units

These two codes exist only on 8 and 9 kW generators with the Evolution 1.0 controller. Code 2102 is set when load is applied, the engine stalls with low voltage, and the unit re-cranks five times. Code 2103 is set after the generator has tried to accept the load ten times and could not. For you, both usually mean the load is too big for a small generator. For 2102, a technician also checks the stepper motor that controls the engine’s throttle. (Generac’s air-cooled manuals do not list a code 2101.)

Code 2299 — Undervoltage Overload

Code 2299 is the “started with too much connected” version. The generator tried to start while a large load was already waiting on it. It could not bring its voltage up to the normal target, so it shut down. Generac lists 2299 for Evolution controllers. Evolution and PowerZone units also have a related alarm called “Low Volts Remove Load.” The owner’s manual gives it the same advice: clear the alarm, remove household loads, put the unit in AUTO, restart, and contact your dealer.

Which Generac controllers show these codes

  • Evolution 1.0 and 2.0: 2100 and 2299. Codes 2102 and 2103 appear only on 8 and 9 kW Evolution 1.0 units.
  • PowerZone 200: 2100 and 2115. PowerZone also logs Undervoltage 1907 when the generator is still overloaded after trying to shed load. It also has a yellow “Overload Cooldown” warning (7000) after five overload shutdowns in a row. The unit runs five minutes with its output off to cool the engine, then powers the house again.
  • Nexus (older units): Nexus controllers do not use these four-digit codes. The Nexus owner’s manual lists Under-frequency (below 50 Hz for more than 30 seconds) and Undervoltage shutdowns. An overload may show up as one of those. Check your owner’s manual.

Why it happens

Most likely first:

  1. Too many big loads at once. Central air conditioning, an electric range, a water heater, a dryer, a well pump, a hot tub or an EV charger each draw a lot. In our experience, motors such as air conditioner compressors and well pumps also pull an extra burst of power for a moment as they start. During an outage they all try to run as if utility power were on.
  2. No load management, or load management that is not working. Generac’s load-shedding devices, such as the Smart A/C Module, Load Managers and Smart Management Modules, watch the frequency of the power the generator makes. When the engine bogs down, they switch off the managed circuits and later bring them back in priority order. If your unit has a load management controller built in, Generac’s installation notice requires any air conditioner it powers to use it. Load shedding may never have been installed, or it may be set to the wrong priority or have failed. Then nothing stops the air conditioner from starting on top of everything else.
  3. The generator is undersized for the home. A finished basement, a second air conditioner, a hot tub or an EV charger added after the install can push the house past the rating.
  4. The engine cannot make full power, or something is shorted. Generac’s test notes say voltage and frequency can be fine with nothing connected but fall when loads come on. There are three reasons. One is a true overload. Another is loss of engine power, for example a fuel supply or throttle problem. The third is a short in the alternator windings or in something connected in the house. (The alternator is the part that turns engine power into electricity.) Only the first is fixed by turning things off. Finding a short takes test equipment, so leave that to a technician.

What you can safely do

  1. Note the code. Write down the alarm name and number from the screen or the Mobile Link app, or take a photo. Note what was running in the house when the generator stopped.
  2. Turn off the big loads. Set the air conditioner thermostat to OFF. Turn off the electric range or oven, dryer, water heater, hot tub, space heaters and EV charger. Use each one’s own switch or control, or its circuit breaker. Do not open any appliance covers or access panels. We suggest leaving the refrigerator, furnace fan, sump pump and lights on.
  3. Clear the alarm once. The buttons depend on your control panel. Text screen with an ENTER button (Evolution): press OFF, then ENTER, then AUTO. Some Evolution manuals say to press ENTER twice, then AUTO instead. Buttons and lights, no text screen (PowerZone 200): press and hold OFF for at least three seconds. When the red light stops flashing and stays solid, press AUTO. Not sure? Check the quick-reference page of your owner’s manual.
  4. Let it pick up the house. In AUTO during an outage, the generator should restart and power the house again. Our advice: bring loads back one at a time, and leave the biggest ones off until utility power returns.
  5. If it comes back, stop. Do not keep clearing it; call us instead. Generac’s manual says an owner can clear an alarm and restart before calling a dealer, and to call if the problem happens again. The controller itself guards against repeat overloads, too. After five overload shutdowns in a row, a PowerZone 200 unit stops powering the house for five minutes so the engine can cool.
Remember: while the alarm is active or the unit is in OFF, your home is not protected from an outage. Get it back to AUTO or call us.

What a GSHA technician checks

  • The real load. With your normal circuits transferred to the generator, we clamp an ammeter on the output and compare the reading to the unit’s rating. This is the first step in Generac’s procedure for 2100 and 2299.
  • Voltage and frequency under load. This tells a true overload apart from a weak engine, a fuel supply that cannot keep up, or a shorted winding or appliance.
  • Load-shedding equipment. We test the Smart A/C Module, Load Managers, Smart Management Modules or Power Management Modules, whichever your system uses. We confirm the air conditioner and other large loads are actually wired to them, and set priorities that make sense for your home.
  • Engine and throttle control. If the measured load is within the rating, Generac’s flow moves on to the engine. That includes the fuel supply and the stepper motor, the small motor that opens and closes the engine’s throttle. On 8 and 9 kW units, Generac’s action for code 2102 also includes inspecting the stepper motor.
  • Current sensor calibration. On Evolution and PowerZone units we confirm the current sensors are calibrated, so the controller is not reporting an overload that is not there.
  • Alarm history and fuel supply. A generator starved for natural gas or propane bogs down under load and can look overloaded.

Load shedding, load management and generator sizing

Load shedding means switching off some circuits on purpose so the generator can carry the rest. Generac’s load management devices do this automatically. They watch the frequency of the power the generator is making. When the engine begins to bog down, the frequency dips and the devices switch off the managed circuits (for example the air conditioner). After a delay of several minutes, they bring them back one priority at a time. A circuit that causes another overload is locked out for a while so the rest of the house keeps running. Generac says Load Managers keep large loads in check at startup and drop them so the generator can recover from an overload. In many cases they let a smaller generator do the job.

Sizing is the other half. A home standby generator is meant for typical household loads — sump pumps, refrigerators, air conditioners, furnaces, electronics and lighting — when it is sized correctly. If your home has grown since the install, repeated overload alarms are how you find out. When we visit, we measure what your house really draws and look at which large loads can be managed. Then we tell you honestly whether load management will solve it or a larger unit is the right call. Learn more about whole-house generator installation and Generac generators.

When to call GSHA Services

  • The Overload Remove Load or Undervoltage Overload alarm comes back after you cleared it once.
  • The alarm appears with only normal loads running, or with the air conditioner off.
  • You see an Overload Cooldown warning, or the generator keeps stopping and restarting during an outage.
  • You are not sure whether your air conditioner or well pump is on load management.
  • You have added a large load (EV charger, hot tub, second AC, addition) since the generator was installed.
  • The generator bogs down, surges or sounds strained under load.

Smell gas? Do not call us first. Leave the area and call your gas utility or 911 from a safe place.

As an authorized Generac dealer, GSHA Services diagnoses overload alarms using Generac’s service procedures. We test and repair load-shedding equipment. When the numbers show it is needed, we install load management modules or a larger generator. We also handle generator repair and annual generator maintenance so problems are found before the next storm.

Request Generac service

Tell us the alarm code and your generator’s model (from the data plate if you have it). Also tell us what was running when it shut down and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions

What does Generac error code 2100 mean?

Code 2100 is Overload Remove Load. The generator was supplying more current than it is rated for, so the controller shut it down to protect the generator. Turn off large appliances, clear the alarm once, and put the unit back in AUTO. If the alarm returns, have a Generac technician check the load and the load-shedding equipment.

Can I just clear an Overload Remove Load alarm and keep going?

Clear it once, after you have turned off the big loads. Generac’s owner’s manual says an owner can clear an alarm and restart before calling a dealer, and to call if it happens again. Generac’s newest controller even forces a five-minute cool-down after five overload shutdowns in a row, so do not keep resetting it.

Why does my Generac overload when the air conditioner starts?

In our experience, an air conditioner pulls a burst of extra power as it starts, often on top of everything else already running. Some Generac units ship with a load management controller inside. For those units, Generac’s installation notice says an air conditioner powered by the generator must be connected to it. Load management switches the AC off when the generator starts to bog down, then brings it back after a delay. If your AC is not on load management, or the module is not working, an overload alarm is the usual result.

What is the difference between code 2100 and code 2299?

Code 2100 means the generator was running and the load rose above its rating. Code 2299, Undervoltage Overload, means the generator tried to start with a large load already connected and could not bring its voltage up to normal. Both are handled the same way: reduce the load, clear the alarm once, and have the load-shedding setup checked if it happens again.

Do I need a bigger generator if I keep getting overload alarms?

Not always. A technician first measures how much power your home actually draws on generator. Then we check whether load management can keep the large loads from starting at the same time. If the total running load is truly above the generator’s rating, a larger unit is the honest answer. Either way, we will tell you which it is.

Generac® and Mobile Link® are trademarks of Generac Power Systems, Inc. GSHA Services, LTD is an authorized Generac dealer. Code descriptions summarize Generac service and owner’s manual information for air-cooled home standby generators; exact names and behavior vary by model, controller and firmware. This page is general guidance for homeowners; always follow the safety instructions in your owner’s manual and on the unit.