Generac RPM Sensor Loss Alarm (Codes 1500–1521): What It Means and What to Do

Your Generac home standby generator shut down or would not start. The display or the Mobile Link® app shows “RPM Sensor Loss” (sometimes written “RPM Sense Loss”). On air-cooled Evolution units, the code that goes with this alarm is 1501, 1505, 1511 or 1515. This page explains what the alarm means in plain language, which checks are safe for you to do, and when it is time to call a Generac technician.

In short: RPM Sensor Loss means the controller (the small computer that runs your generator) lost the engine-speed signal. That happened either while it was trying to start or while the engine was running. Common causes are an engine that never turned over (weak battery, starter or fuse), air or dirt in the fuel, or a missing pulse from an ignition coil. Clear the alarm once; if it comes back, call GSHA Services.
Safety first. Never open panels or touch wiring. In AUTO, the generator can start on its own at any time. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Never run a generator indoors or in or near a garage, and keep a working carbon monoxide alarm in your home.

What this alarm means

Every time your generator starts, the controller listens for a signal that tells it how fast the engine is turning. On Generac air-cooled units with an Evolution controller (Evolution 1.0 and 2.0), that signal comes from the ignition magnetos — the parts that make the spark. It travels over a single wire into the control panel. The controller uses it to know when to stop the starter, when to open the fuel valve and when the engine is running normally.

For air-cooled Evolution units, Generac’s service manual describes the alarm this way:

  • While cranking: if the controller does not see a valid speed signal within about three seconds, it stops and locks out with “RPM Sensor Loss” on the display.
  • While running: if the signal drops out for a full second, the controller shuts the engine down, waits 15 seconds and tries to start it again. If the signal is lost a second time, it allows one more restart attempt. Then it locks out with the alarm on the screen.

Liquid-cooled units are generators whose engine is cooled with coolant and a radiator, much like a car engine. They use slightly different timing. The controller waits four seconds for a signal while cranking. After a running shutdown, it allows two more restart attempts before locking out. Generac’s liquid-cooled service manual also notes that this automatic restart happens only in AUTO; it will not re-crank in MANUAL. On any model, if you are not sure, check your owner’s manual.

That is why the owner’s manual lists two different symptoms for the same alarm. Either the unit shut down while running and tried to restart, or it would not start in AUTO when the power went out. In both cases the red alarm light comes on (it flashes on current 10–28 kW models). Until the alarm is fixed and cleared, the generator will not protect your home during an outage.

One important point: the alarm name makes it sound like a sensor broke. In practice, Generac’s service manual notes that a common cause is that the engine did not crank at all. A weak battery, a faulty starter or a problem in the crank circuit (the relay and wiring that send battery power to the starter) can all cause that. The controller waited for a speed signal that never came.

Which code you will see

On air-cooled Evolution units, the code number tells a technician which engine type you have. It also shows whether the signal was lost while cranking or while running. Liquid-cooled units and units with the Power Zone® 200 controller use their own numbers for the same alarm. The codes you may see are:

CodeController / engineWhen it happenedCauses listed by Generac
1500Liquid-cooled units with Evolution control AlarmNot specifiedMissing pulses from the magnetic speed pickup — the small sensor on liquid-cooled engines that reads engine speed. A technician diagnoses this.
1501Evolution, twin-cylinder (V-twin) engine AlarmRunningAir pocket in the fuel line, dirty fuel, or a missing ignition pulse (one of the two ignition coils not firing).
1505Evolution, twin-cylinder engine AlarmCrankingStarter motor problem or a missing ignition pulse. If the engine did not turn at all, the alarm log may also show “No Rotation Warning.”
1511Evolution, single-cylinder engine (8–10 kW units) AlarmRunningAir pocket in the fuel line, dirty fuel, or loss of the ignition pulse.
1515Evolution, single-cylinder engine AlarmCrankingStarter motor and/or engine problem, or loss of the ignition pulse. May be logged with “No Rotation Warning.”
1516–1521Liquid-cooled units with Evolution control AlarmCranking or runningSame alarm family. Generac ties 1516 and 1517 to low fuel pressure while cranking or running, with the same ignition, air-pocket and dirty-fuel causes as above. Codes 1518–1521 mean the speed sensor sent no pulses, or missed pulses, while cranking or running. Possible causes include the starter circuit, sensor alignment or a low battery. A technician diagnoses these.
1522Power Zone 200 controller (used on newer air-cooled units) AlarmAfter the start commandThe crankshaft position sensor (a small sensor that reads engine speed from the crankshaft) measured zero speed. The signal from the alternator’s excitation winding (the “DPE” winding, a coil inside the part that makes electricity) also read zero. The action step Generac lists is a battery and cables test.
—Nexus (older units) AlarmCranking or runningShows “RPM SENSE LOSS” on the screen with no code number. Same causes as the Evolution codes above.

Code details summarize Generac diagnostic manuals for air-cooled and liquid-cooled home standby generators. Names vary slightly by controller and firmware: the display may say “RPM Sensor Loss” while the alarm log says “RPM Sense Loss.” Not sure which controller you have? Evolution and Nexus controllers have a small text screen with buttons. Current 10–28 kW units show alarms with LED lights on the unit and in the Mobile Link app. A photo of the data plate helps us identify your model.

Why it happens

Here are the causes Generac lists for this alarm, starting with the most common:

  1. The engine never turned over. A weak or dead battery, a starter problem or a fault in the crank circuit means there is no engine speed to sense. If the controller’s 7.5-amp fuse is blown, a manual start attempt also ends in RPM Sense Loss. When the engine did not crank, the alarm log may also show “No Rotation Warning,” and the battery check may show a problem.
  2. Air in the fuel line or dirty fuel (running codes 1501 and 1511). Generac lists both as causes when the alarm happens while the engine is running. Either one can interrupt the engine and the speed signal. Generac’s test flow for these codes includes checking the fuel supply and the gas pressure at the generator, for natural gas or propane.
  3. A missing ignition pulse. Twin-cylinder engines have two ignition coils. Generac lists the loss of one coil as a cause of this alarm. Single-cylinder engines can lose their ignition pulse too.
  4. The speed-signal wire or the magnetos. The signal travels from the ignition magnetos to the controller on one wire. If that wire is damaged, shorted or broken, the controller sees nothing. If the magnetos are not producing the signal, a technician checks and adjusts them.
  5. Starter motor or engine trouble while cranking (codes 1505 and 1515). Generac lists a starter motor problem for both codes, and an engine problem for single-cylinder units.
  6. On Power Zone 200 units (code 1522), the crankshaft position sensor and the alternator’s excitation winding both read zero after the start command. The action step Generac lists is a battery and cables test.
  7. On liquid-cooled units (codes 1500 and 1516–1521), the magnetic speed pickup did not send pulses, or fuel pressure was low while the engine cranked or ran.

How is this related to “No Rotation Warning”?

“No Rotation Warning” is a separate message. Generac’s service manual groups it with the cranking codes 1505 and 1515 under the case where the engine does not crank. If the engine cranks, the technician checks the speed-signal wire. If the engine does not crank, the technician works through the starting system — fuse, battery and cables, crank relay, starter contactor and starter motor. So if your alarm log shows both messages, the engine most likely never turned. The battery and starter are the first things to look at.

What you can safely do

These checks are safe with the generator set to OFF and without opening any panels. Do not open the control console, touch the fuse or the battery, or try to jump-start the unit.

  1. Note the alarm and the code. Take a photo of the display or the Mobile Link screen. Look at the alarms shown in the app, or in the alarm log on the controller screen if your unit has one. If “No Rotation Warning” or a battery message also appears, tell us when you call.
  2. Check the battery condition. In the current owner’s manual, the step for a unit that will not start with this alarm is to check battery condition in the Mobile Link app. Older Evolution owner’s manuals say to check the BATTERY menu on the controller screen instead. If it says CHECK BATTERY, the battery needs to be replaced; a technician can test and replace it. If it shows GOOD, the manual says to contact a service dealer.
  3. Did it crank? If you were nearby when the outage started, note whether you heard the engine try to turn over. Silence points to the battery, fuse or starter. Cranking without starting points to the ignition or speed-signal side.
  4. Check the fuel supply. Make sure the gas shutoff valve to the generator is open. If you use propane, check the tank gauge. Do not touch the gas regulator (the device that sets the gas pressure) or any fitting.
  5. Turn off large loads. If the generator was powering your home when it shut down, switch off big appliances before you restart it. Think central air, an electric range, a dryer or a well pump. Use the thermostat, the appliance’s own switch, or its breaker; never remove a panel cover. The owner’s manual lists this step for RPM Sense Loss.
  6. Clear the alarm once. On current 10–28 kW models, press and hold OFF for at least three seconds until the red OFF light stays solid. On Evolution controllers, press OFF and then ENTER. Some older owner’s manuals list a different button order, so follow yours if it differs. Then press AUTO. If the generator starts and runs, keep an eye on it and book a check-up.
  7. If the alarm comes back, stop. Do not keep clearing it. Generac limits crank attempts to prevent damage, and clearing again will not fix the cause. Call GSHA Services.
Remember: while the generator is in OFF or an alarm is active, your home is not protected during a power outage. Get it back to AUTO or call us.

What a GSHA technician checks

We follow Generac’s diagnostic flow for this alarm rather than guessing. Depending on your code and what the alarm log shows, a visit usually covers:

  • Whether the engine actually cranks. We test the battery and check the cables and the controller fuse. Then we check the crank relay, the starter contactor (the heavy switch that feeds battery power to the starter) and the starter motor.
  • Fuel supply and pressure at the generator for natural gas or propane. That includes the regulator and whether the gas line is sized correctly.
  • The engine-speed signal — the pulse from the ignition magnetos to the controller, the condition of the signal wire, and the magnetos themselves, which may need adjusting.
  • The ignition coils, since Generac lists a missing ignition pulse as a cause.
  • On Power Zone 200 units, the battery and cables, which is the action step Generac lists for code 1522. On liquid-cooled units, the speed sensor and its wiring, plus fuel pressure while cranking and running.
  • Clearing the alarm and a test run, then setting the unit back to AUTO so it is ready.

When to call GSHA Services

  • The RPM Sensor Loss alarm came back after you cleared it once.
  • The generator did not crank at all, or the battery condition shows a problem.
  • The battery shows good in the app or in the controller’s battery menu, but the unit still will not start. The owner’s manual says to contact a service dealer at this point.
  • The unit shut down during an outage while powering your home.
  • You see code 1522 on a Power Zone 200 unit, or code 1500 or a 1516–1521 code on a liquid-cooled unit.
  • You smell gas — leave the area first, call the gas utility or 911, then call us after it is safe.

As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators using Generac service procedures and genuine parts. We also perform annual maintenance, so a weak battery or fuel problem is less likely to surprise you in the next storm. Learn more about our generator repair, generator tune-up and Generac generator installation services.

Request Generac service

Tell us the alarm and code (for example “RPM Sensor Loss 1505”) and whether the engine cranked. If you have it, add your model number from the data plate and the best time to reach you. For an urgent problem during an outage, please call (224) 220-3660.

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions

What does Generac error code 1501 mean?

Code 1501 is RPM Sensor Loss on a twin-cylinder Evolution unit that was running. Generac lists an air pocket in the fuel line, dirty fuel, or one ignition coil not firing as the causes. Clear the alarm once as your owner’s manual describes. If it comes back, call a Generac technician.

What do Generac codes 1505 and 1515 mean?

These are the cranking versions of RPM Sensor Loss: 1505 for twin-cylinder engines and 1515 for single-cylinder engines. The controller did not see an engine speed signal within about three seconds of starting to crank. A common cause is an engine that never turned over, from a weak battery, a starter problem or a blown controller fuse. A missing ignition pulse can also cause it. If the alarm log also shows No Rotation Warning, the engine most likely did not crank.

Is the RPM sensor a part I can replace myself?

On air-cooled Evolution units there is no separate sensor to swap. The speed signal comes from the ignition magnetos over a wire. The fix depends on what is actually missing: battery, starter, fuel, ignition or wiring. Power Zone 200 units do have a crankshaft position sensor, but the action step Generac lists for code 1522 is a battery and cables test. Leave this diagnosis to a technician.

Why did my Generac restart on its own after showing RPM Sensor Loss?

That is normal controller behavior. If the speed signal drops out while the engine is running, the controller shuts down, waits 15 seconds and cranks again. Air-cooled Evolution units allow one more restart and liquid-cooled units allow two. If the signal is lost again, the controller locks out with the alarm. The Generac liquid-cooled service manual notes that this automatic restart happens only in AUTO, not in MANUAL. Even if it restarted, have the cause found before the next outage.

How do I clear the RPM Sensor Loss alarm?

On current 10 to 28 kW models, press and hold OFF for at least three seconds until the red OFF light stays solid, then press AUTO. On Evolution controllers, press OFF, then ENTER, then AUTO. Some older owner’s manuals list a different button order, so follow yours if it differs. Clear the alarm only once. If the same alarm returns, stop and call a Generac technician.