Generac Low Oil Pressure Alarm (Code 1300): What It Means and What to Do

Your Generac home standby generator stopped and the red alarm light came on (it flashes on the newest units). The display or the Mobile Link app says “Low Oil Pressure”, usually with the code 1300. This page explains what the alarm means and why it usually happens. It also covers what you can safely check yourself, and what our technicians look at when they come out.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Serving Chicagoland & southeastern Wisconsin
In short: Code 1300 means the generator shut itself down because the engine’s oil pressure dropped too low. The most common reason is a low oil level, especially after the generator has run for days during an outage. With the unit in OFF, check the oil, clear the alarm once, and call for service if the oil was low or the alarm comes back.
Safety first. A generator in AUTO can start on its own at any time. Open the lid and press OFF before you remove the front panel, and never touch wiring. The engine and exhaust stay hot for a while after running. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Never run a generator indoors or near an open window or garage, and keep a working carbon monoxide alarm in your home.

What the Low Oil Pressure alarm means

Every Generac air-cooled home standby generator has a small oil pressure switch on the engine (near the oil filter on Evolution units). While the engine runs, oil pressure holds the switch in its running position. If the pressure falls below the switch’s set point, the switch changes state. The controller — the small computer inside the generator — then cuts the fuel and the ignition and stops the engine. That is on purpose. Generac builds in these protective switches to prevent engine damage when nobody is watching the unit.

The controller then latches the alarm — it holds the alarm until someone clears it. The red alarm light comes on (it flashes on the newest units), and the screen or Mobile Link shows “Low Oil Pressure” and, on Evolution units, the code 1300. The generator will not start on its own in AUTO during an outage until the alarm is cleared. On Evolution controllers, this is different from a High Temperature alarm, which resets itself once the engine cools. A Low Oil Pressure alarm stays until someone clears it.

Generac’s service manual describes 1300 as the alarm for low oil pressure that happened while the unit was running, and its first advice is short: check the oil level and the oil pressure. One pattern technicians look for: the engine cranks, starts, runs for about five to ten seconds, and then stops with this alarm. Generac’s manual says that points to a low oil level, low oil pressure, or a bad oil pressure switch.

Which Generac controllers show this alarm

  • Evolution 1.0 and Evolution 2.0 controllers show “Low Oil Pressure” with E-code 1300 (the E-code is the number on the screen). The two versions use different oil pressure switch types and slightly different trip points. That matters for the repair, not for what you see on the screen.
  • Nexus controllers (older units) show the words “Low Oil Pressure” on the display without a number.
  • PowerZone 200 controllers (the newest 10–28 kW air-cooled units) show the alarm in the Mobile Link app and with a flashing red light. Generac’s PowerZone service manual lists it as an Engine Oil Pressure Alarm (3301). These units also have an oil level sensor. It can post a separate Low Oil Level warning (2126). A warning does not shut the generator down, but it is a condition to fix — do not ignore it.

Why it happens

Most likely causes first:

  1. The oil level is low. Engines use some oil while they run. During a long outage the generator may run for days without a break, and the level can drop far enough to trip the alarm. Generac’s owner’s manual says plainly that the generator will shut down if the oil level is low. It asks owners to check the oil every day when the unit runs for extended periods. Oil can also go missing through a leak — a worn seal, gasket or hose, or an engine breather problem. Using the wrong type or thickness of oil can make the engine use more oil, and the manual says the wrong oil can damage the engine. That is why it asks you to check the type and amount before the engine is started.
  2. The oil pressure really is low even though the level is fine. Something is wrong inside the engine’s lubrication system — the parts that move oil through the engine. Generac’s service manual says the engine should be shut down right away in this case. It should not run again until a technician finds the cause.
  3. The oil pressure switch has failed. The switch is a simple part. If it sticks or fails, it can report low pressure when the pressure is actually fine.
  4. A wiring problem. The wire that runs from the switch to the controller can break, come loose, or short to ground. Any of these can cause a false alarm.
  5. Mismatched parts after a repair. Evolution 1.0 and Evolution 2.0 use opposite switch types. One is closed when there is no oil pressure; the other is open. Generac’s manual tells technicians to confirm the switch and controller part numbers match before going further.
  6. Rarely, the controller itself. If the oil pressure, the switch and the wiring all test good, the controller is the last suspect.

Too much oil is not good either. Overfilling can cause oil to leak. The level belongs at the FULL mark on the dipstick, never above it.

What you can safely do

  1. Write down the alarm. Note the alarm name, the code, and the date and time it happened. Or take a photo of the screen or the Mobile Link app. If the generator had been running for a long stretch during an outage, tell us. It points to the most likely cause.
  2. Turn the generator off the way your owner’s manual shows. With the unit in OFF it cannot start on its own. Lift the lid, press OFF, and wait five minutes before you remove the front panel. If the unit is still running, the current owner’s manual for the 10–28 kW units says to first switch the generator’s own main breaker (Generac calls it the generator disconnect) to OFF, press SERVICE and check that the blue light is on, and let the engine run for about a minute to cool down before you press OFF. On older Evolution units with a screen, press OFF. Check the manual for your model.
  3. Check the oil level if you are comfortable doing it. Remove the front panel the way your manual shows. Pull the dipstick, wipe it clean, push it all the way in, and pull it out again. The oil should reach the FULL mark. While the panel is off, look for fresh oil on the engine, inside the enclosure or on the pad underneath. A wet, oily spot means a leak.
  4. If the oil is low, the safest choice is to leave the unit in OFF and call us. If you have the correct oil on hand and your manual shows how, you may add a little at a time. Stop when the level reaches the FULL mark — never above it. The correct oil depends on your model: the current owner’s manual for the 10–28 kW units calls for Generac’s own 5W-20 oil made for gas-fueled engines after break-in, many earlier Evolution units call for synthetic 5W-30, and 2013-era units choose the oil by outdoor temperature. Check your manual. If you are not sure which oil to use or how much to add, leave it and call. Even if you top it up, plan on a service visit. We need to find out where the oil went.
  5. Clear the alarm once and go back to AUTO. Put the front panel back on. On the newest 10–28 kW units, press and hold OFF for at least three seconds. The red light stops flashing and stays solid when the alarm is cleared. On Evolution units with a screen, press OFF and then ENTER. Then press AUTO. If you turned the generator’s main breaker off, switch it back to ON. If you pressed SERVICE, press it again and check that the blue light is off. Close and lock the lid. The green light should come on.
  6. If the alarm comes back, stop. Do not clear it a second time. Leave the unit in OFF and call us. Generac’s service manual says that when oil pressure is truly low, the engine must be shut down right away. There is a problem in the lubrication system.
Remember: while the alarm is active or the unit is in OFF, your home is not protected during a power outage. If you cannot get the generator back to AUTO with a green light, call us the same day.

What a GSHA technician checks

  • The controller’s alarm log and run log — how long the unit ran before it shut down, and whether anything else happened first. A shutdown after ten days of running tells a very different story than one right after start-up.
  • Oil level, oil condition and leaks — we confirm the level, look for the cause of any oil loss, and make sure the correct oil is in the engine.
  • Actual oil pressure — we install a mechanical gauge in place of the switch and compare the reading with Generac’s normal running range. If pressure is truly low, the engine stays off and the lubrication problem is diagnosed before anything else is touched.
  • The oil pressure switch — we test it with a meter both at rest and with the engine building pressure. We also confirm the switch type matches the controller version.
  • The wiring between the switch and the controller — we check for a broken wire, a short to ground or a bad connection. We also confirm the controller actually sees the switch change state.
  • The controller — only if everything above passes. We then clear the alarm, run the generator, and verify it returns to AUTO with a green light.

If the engine simply used its oil during a long run, the visit is usually simple. We top up or change the oil, replace the filter if it is due, and reset the maintenance reminder. Generac’s Schedule A service (oil, oil filter and a battery check) is due every two years or 200 run hours. In cold weather below 40 °F, Generac says to change the oil and filter every year or 100 hours — which describes most Chicagoland winters. A regular generator tune-up is the easiest way to keep this alarm from showing up in the middle of a storm.

When to call GSHA Services

  • The oil was low when you checked it, even if you topped it up.
  • The alarm came back after you cleared it once.
  • You see oil under the generator, inside the enclosure or on the engine.
  • The generator ran for several days during an outage and has not been serviced since.
  • You are not comfortable removing the front panel or checking the dipstick, or you are not sure which oil to use.
  • The unit is overdue for maintenance or it has been more than a year since the last service.

As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators using Generac’s own service procedures and genuine parts. We also handle warranty repairs on qualifying units and perform annual maintenance. Learn more about our generator repair, generator maintenance and Generac generator installation services.

Request Generac service

Tell us the alarm on your generator (Low Oil Pressure, 1300) and the model from the data plate (the sticker with the model and serial number) if you have it. Let us know whether the oil was low and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Frequently asked questions

What does Generac code 1300 mean?

Code 1300 is the Low Oil Pressure alarm on Generac air-cooled home standby generators with an Evolution controller. Oil pressure in the engine dropped below the set point of the oil pressure switch, so the controller shut the engine down to protect it. The alarm latches: the generator will not start on its own in AUTO until it is cleared.

Can I just add oil and reset the generator?

If the oil was low and your owner’s manual shows how, you can add the correct oil to the FULL mark with the unit in OFF, then clear the alarm once and put it back in AUTO. If you are not sure which oil to use, leave the unit in OFF and call. Either way, a low level after a Low Oil Pressure alarm still needs a service visit, because the oil went somewhere. Either the engine used it during a long run or it is leaking. If the alarm returns after one reset, leave the unit in OFF and call a technician.

Why did my generator show Low Oil Pressure after running for several days?

Engines use some oil while they run. Over a long outage the level can drop enough to trip the alarm. Generac asks owners to check the oil every day when the generator runs for extended periods. If your unit ran for days and then shut down on code 1300, low oil level is the most likely cause. The unit is probably also due for an oil and filter change.

What oil does a Generac home standby generator use?

It depends on the model and year, so check your owner’s manual. The current owner’s manual for the 10 to 28 kW units calls for Generac’s own 5W-20 oil made for gas-fueled engines after the 25-hour break-in period, and says not to use special additives. Many earlier Evolution units call for synthetic SAE 5W-30 for all temperatures, and some 2013-era units choose the oil by outdoor temperature. Whatever the type, never fill above the FULL mark on the dipstick.

Does the generator restart on its own after a Low Oil Pressure alarm?

No. Low Oil Pressure is a latching alarm. The generator stays shut down and will not start in AUTO during an outage until the alarm is cleared at the control panel. On Evolution controllers that is different from a High Temperature alarm, which clears itself once the engine cools.