Generac Mobile Link Alerts Explained: Low Fuel Pressure, Emergency Shutdown, Offline and More

Your phone just buzzed with a message from the Mobile Link® app. Maybe it is a low fuel pressure warning, a note that the generator “has been stopped via generator emergency shutdown switch,” or a message that your generator is offline. This guide explains what the most common Mobile Link alerts on a Generac® home standby generator mean. It also shows which ones need action right away and which can wait for a service visit.

  • Authorized Generac dealer
  • Generac-trained technicians
  • Service, repair & maintenance on all Generac home standby models
  • Serving Chicagoland & southeastern Wisconsin
In short: Most Mobile Link alerts pass along an alarm or warning from the generator’s controller (its built-in computer). A red alarm means the generator has shut down to protect itself; a yellow warning or maintenance notice means it can still run but needs attention. An offline message means the generator has lost its connection to Generac’s servers, so alerts stop until the connection is fixed.
Safety first. A home standby generator in AUTO can start on its own at any moment, including during its scheduled exercise. Never open panels or touch wiring. If you smell gas, leave the area and call your gas utility or 911 from a safe place. Never run a generator indoors or in or near a garage or window, and keep a working carbon monoxide alarm in your home.

How Mobile Link alerts work

Mobile Link is Generac’s remote monitoring system. A connectivity device on the generator sends its status to Generac’s servers. Depending on the age and model, that device is a Wi-Fi module or a cellular connectivity accessory. On current units the connectivity accessory can use cellular or your home Wi-Fi. The app or website shows the current status, active alarms and warnings, maintenance due, run hours, battery voltage and the exercise schedule. The dashboard uses a simple color code. Green is ready, blue is running, yellow needs maintenance but can still run, and red has a problem and needs service.

With an active Mobile Link subscription, you can get a push notification, text or email when the generator’s controller raises an alarm or warning. The alert names usually correspond to the generator’s own alarm and warning names, and the Generac error code list covers each one. You can adjust how and how often some alerts arrive. Generac’s Mobile Link manual describes getting them right away or in a daily, weekly or monthly summary. A summary can include maintenance reminders, faults, warnings and exercise confirmations. On current units, a technician can put the generator in SERVICE mode. That pauses Mobile Link notifications and locks out remote start commands, so a quiet app during a service visit is normal. Mobile Link also lets you choose a preferred servicing dealer so their contact details are in the app.

“Low fuel pressure” alert

What it means

The controller is reporting that the gas pressure feeding the engine is lower than it should be. The label depends on the controller:

  • PowerZone 200 (the newest air-cooled units) reports Engine Fuel Delivery Pressure. Code 3217 is a warning (pressure a little below normal). Code 3201 is an alarm (pressure well below normal) that stops the generator.
  • Evolution 2.0 lists Fuel Pressure among its warning messages.
  • Evolution 1.0 menus list a Fuel Warning.
  • Older controllers may not show a separate fuel pressure message; check your owner’s manual. On any unit, a fuel supply problem can also show up as a no-start (Overcrank), hard starting or rough running.

The engine needs an adequate gas supply to start and run. Generac lists incorrect fuel pressure as a cause of hard starting and rough running, and a low fuel supply as one cause of the Underspeed alarm. So a starved engine can end in a no-start (Overcrank) or a shutdown in the middle of an outage.

Why it happens

  • The fuel shutoff valve in the gas supply line is not fully on.
  • A propane tank is running low or empty.
  • The supply cannot keep up under load. The gas piping may be undersized or restricted. The regulator (the device that lowers gas pressure for the engine) may be too small or mounted too close to the generator. Generac’s installation manual says fuel pressure must never drop below specification once the generator is installed.
  • On PowerZone 200 units, the fuel pressure sensor or its wiring is faulty (a technician tests this).

What you can safely do

  1. Note the message and the time. A screenshot of the alert helps our technician.
  2. Check the fuel shutoff valve. Make sure the fuel shutoff valve in the gas supply line to the generator is ON (open). Do not remove any panels; the shutoff valve inside the enclosure is technician work.
  3. Propane owners: check the tank gauge. If it is low, call your propane supplier first.
  4. Do not touch the regulator, the gas piping or any fittings. Fuel pressure is measured with a gauge by a technician.
  5. If the generator is in alarm and the fuel supply is now fixed, clear it once. On current units, hold OFF for about three seconds until the red light stops flashing, then press AUTO. On Evolution controllers with a display, press OFF, then ENTER, then AUTO. If the alert comes back, stop and call us.
Not the same as a low propane tank. A propane level reading in Mobile Link comes from an optional tank monitor that can be linked to the app. A fuel pressure alert comes from the generator itself. A low tank can cause low pressure, but so can a supply or regulator problem with a full tank.

“Generator has been stopped via generator emergency shutdown switch”

What it means

Generac home standby generators have an emergency shutdown switch on the outside of the enclosure, so the unit can be shut down without opening it. It is on the side panel of current units and on the back panel of many Evolution units. Some Evolution manuals call it the auxiliary shutdown switch. When the switch is turned off, the generator shuts down and will not restart until the switch is set back to CLOSED (I) and the alarm is cleared. On current units the Mobile Link app shows the exact message “Generator has been stopped via generator emergency shutdown switch”. The red light on the side of the unit also flashes.

How the alarm is named depends on the controller:

  • Current (PowerZone 200) units have no text display, so the alarm appears in the app and in the dealer’s Field Pro app. Code 2800 means the switch on the unit was used; Generac’s PowerZone 200 service manual calls it Emergency Shutdown Pressed. Code 2801 means a remote emergency stop (if one is installed) was activated; the service manual calls it Auxiliary Shutdown. The owner’s manual chart lists both codes as Shutdown Switch.
  • Evolution units show Shutdown Switch on the display, with code 2800. Generac’s Evolution service manual lists the same code as Aux Shutdown. Evolution alarm lists also include a separate Emergency Stop alarm; if you see that name instead, call us.

Why it happens

  • Someone turned the switch off, for example by accident while working near the unit.
  • Some larger Evolution-era models also have a second shutdown switch inside the enclosure. Generac’s manuals put the cutoff at 14 or 15 kW and up, depending on the model line, so check your owner’s manual. Both switches must be ON; a technician checks the inside one.
  • On current units, a remote emergency stop was activated, or its wiring or jumper has a problem (code 2801).
  • The switch or its wiring to the controller has failed (a technician checks this).

What you can safely do

  1. Find the emergency shutdown switch on the outside of the enclosure (side panel on current units, back panel on many Evolution units) and set it back to CLOSED (I), the ON position.
  2. Open the lid and hold the OFF button for about three seconds. The red light should stop flashing and stay solid, which means the alarm is cleared. On Evolution controllers with a display, press OFF, then ENTER instead.
  3. Press AUTO. Once the app refreshes, it should show the generator as ready.
  4. Only once. If the alert comes back and nobody touched the switch, or the app shows code 2801, call us.
Do not use the emergency shutdown switch to turn the generator off for routine reasons. Generac warns that doing so can damage the unit. If you need the generator off during an outage, use the shutdown steps in your owner’s manual, or call us.

Alarm and warning alerts that mirror the generator

Most Mobile Link alerts are the generator’s own alarms and warnings delivered to your phone. An alarm shuts the generator down to protect it; a warning flags something that should be fixed but does not stop the unit. Generac’s owner’s manual says an owner can clear an alarm and restart before calling a dealer, and should call if the problem comes back. Our advice is to clear it only once. These are the alerts homeowners ask us about most; the full code list has the rest.

Alert in the appTypeWhat it meansWhat you can do
Warming Up (for several minutes), then Under VoltageAlarmThe generator ran a cleaning cycle because its output voltage came up low — frost or dust on internal electrical connections — and the cycle did not clear it.After a few minutes, clear the alarm once and restart. If it happens again, make no further attempts and call us.
Low Oil PressureAlarmOil pressure dropped too low and the engine shut down to protect itself.With the unit in OFF, check the oil level. If it is low or the alarm returns, call us before running it again.
OvercrankAlarmThe engine cranked through all its attempts without starting.Check that the fuel shutoff valve in the gas supply line is ON and the propane tank has fuel. Do not remove panels. Clear once. If it still will not start or runs rough, call us.
High TemperatureAlarmThe engine got too hot, usually because air cannot flow through the enclosure.With the unit in OFF and cooled down, clear leaves, snow, grass or nests from around the intake, exhaust and rear of the unit. Do not touch hot surfaces. If nothing is blocked, call us.
Overload Remove LoadAlarmYour home asked for more power than the generator can deliver.Turn off large appliances, clear the alarm, put it back in AUTO and restart.
Low Battery / Battery Problem / Charger Warning / Charger Missing ACWarningThe battery or its built-in charger needs attention. The generator can still run for now, but a weak battery can keep it from starting.Check the battery condition shown in the app and schedule service. See the battery and charger messages.
Service A / Service B / Service C / Inspect BatteryMaintenanceRoutine maintenance is due. Schedule A is oil, filter and battery check; Schedule B adds the air cleaner and spark plugs; Schedule C is the first oil change at 25 run hours. Only one maintenance alert shows at a time.Book a generator tune-up. After the service, the reminder is cleared with “Clear Maintenance” in the app.
Exercise Set ErrorWarningThe exercise schedule needs attention. One Generac diagnostic manual defines it as an exercise time that has never been set, so the generator may not be running its regular test.On Evolution units, the exercise time is set at the control panel. On current units a technician sets it with Field Pro, so ask us at your next visit.

Alarm names follow Generac’s air-cooled owner’s manuals for Evolution and PowerZone 200 controllers. Your model, controller and app version may word them slightly differently.

Exercise notifications

A home standby generator runs itself on a schedule to keep the engine, battery and controls ready. Generac calls this the exercise. How often and how long it runs depends on the model:

  • Current (PowerZone 200) units: weekly, biweekly or monthly, for 5 to 20 minutes (5 by default). The schedule is set with the dealer’s Field Pro app.
  • Many Evolution units: weekly, biweekly or monthly. Depending on the model, each run lasts about 5 or 12 minutes. The schedule is set at the control panel.
  • Older units: Generac’s 2010 and 2013 owner’s manuals describe an exercise every seven days, about 12 minutes long.

On some models the engine runs at a lower “Quiet-Test” speed during the exercise. Generac offers it only on certain models, and it can be turned off. Normally your house stays on utility power during the exercise. On Evolution and older units, the house moves to generator power during an exercise only if utility power is lost. Current units have a “Transfer on Scheduled Exercise” option, off by default, which moves the house onto generator power every 3, 6 or 12 months.

Mobile Link can include exercise confirmations in alert summaries, and the app keeps a run history so you can see when the last exercise ran. On current units, Mobile Link also offers Exercise Now (the house stays on utility power) and Exercise Now with Transfer (the house runs on generator power during the test). Generac’s earlier Mobile Link guides also describe setting the exercise time from the app or website.

If the exercise you expected did not show up

  • The generator must be in AUTO. It will not exercise in OFF or MANUAL, and it will not exercise if it is already running.
  • The clock may be wrong. If the battery was disconnected or the controller lost power, the date and time may need to be reset. On current units, an internet connection keeps the clock and daylight saving time correct; without one, a technician resets the clock with Field Pro. On Evolution units the date and time are set at the control panel.
  • Check the app’s run history before you worry. A missed notification is not always a missed exercise.
Heads-up: once an exercise schedule is set, the generator cranks and starts on its own at that day and time, every interval. That is normal, and one more reason never to work on or near the unit while it is in AUTO.

Offline, disconnected or no Wi-Fi

An offline message means Mobile Link has lost contact with the generator’s connectivity device, the Wi-Fi module or cellular accessory that links it to Generac’s servers. Common causes are a power outage at your router, a change to your home network, weak Wi-Fi or poor cellular coverage. It can also be a hardware problem, such as no power to the module, a blown fuse in its harness or a loose connection at the controller. Those are checks for a technician. While the generator is offline, it cannot send you alarms. It also cannot download controller updates or correct its exercise clock for daylight saving time on its own. So it is worth fixing, and in the meantime it is a good idea to look at the lights on the generator in person.

Wi-Fi connections

  • Power outage. If your router has no power, the generator has no internet. Generac’s guidance is simply to wait for utility or backup power to return.
  • New router, new internet provider or new Wi-Fi password. Any change to the home network means the generator must be reconnected. On Evolution units with a Wi-Fi module, this is done from the WIFI menu on the generator’s display (“REDO WIFI SETUP?”), which opens a 30-minute window to connect. On current units, follow the connectivity accessory’s own manual, or a technician can configure Wi-Fi with Field Pro.
  • Weak signal. The Wi-Fi module works only on 2.4 GHz Wi-Fi networks, not 5 GHz, and needs ports 80 and 443 open, which most home routers allow by default. A Wi-Fi extender placed about halfway between the router and the generator helps; placing it next to either one does not.
  • Controller warnings. Evolution 2.0 can show No WIFI Module, No WIFI Router Comms or No WIFI Server Comms. The WIFI menu’s status line says where the chain breaks. Router Timeout means it is not reaching your router. Time Server Denied means it reached the router but not Generac’s server. Wi-Fi Module Missing/Disconnected points to the module itself, which is a technician check.

Cellular connections

  • Coverage. A cellular device needs usable signal where the generator sits. Generac’s Mobile Link cellular manual suggests a simple test: make a phone call while standing next to the unit. That manual also mentions a network extender for weak areas, and says a “Suspended” status is handled by Mobile Link customer service.
  • Waiting on the server. Sometimes the device has signal but has not yet reached Generac’s server. For earlier Mobile Link cellular units, Generac’s troubleshooting guide says the device retries for about an hour, rests for an hour, and tries again. Switching the generator from OFF to AUTO ends the rest period early. Often the fix is simply to wait.
  • Current units. The connectivity accessory on current units can connect by cellular or by your home Wi-Fi. If it will not connect, a technician can test it and its link to the controller, and can configure Wi-Fi with Field Pro.

What you can safely do

  1. Check that your home has power and internet. Restart the router if other devices are offline too.
  2. Check the generator in person. Look at its status lights. On Evolution units with Wi-Fi, open the lid (not the panels) and check the WIFI menu on the display; it shows signal strength and whether the connection is OK.
  3. If your network changed, redo the Wi-Fi setup on Evolution units. For current units, see the connectivity accessory’s manual or call us.
  4. Give a cellular device an hour or two after an outage or a network hiccup before assuming it has failed. Do not try to reset the Wi-Fi module to factory settings; Generac makes that a dealer-only step.

What a GSHA technician checks

  • Fuel pressure: measures static and running gas pressure at the generator with a manometer (a gas pressure gauge), including under load. Checks the supply, regulator and gas line size against Generac’s specifications for natural gas or propane.
  • Fuel pressure sensor and fuel setting: tests the sensor and wiring on PowerZone 200 units and confirms the controller is set for the fuel you actually have.
  • Emergency shutdown circuit: tests the outside switch and, on Evolution-era models that have one, the inside switch. Also checks the shutdown-switch wiring and connector at the controller, and any remote stop kit or jumper.
  • Connectivity and firmware: confirms the Wi-Fi module or connectivity accessory has power and is talking to the controller, checks its fuse and harness connection, and checks signal strength at the unit. On current units, uses Field Pro to test the connection, configure Wi-Fi where needed, review the alarm log and update firmware where Generac calls for it.

When to call GSHA Services

  • A low fuel pressure alert with the fuel shutoff valve ON and the propane tank full, or one that repeats.
  • The emergency shutdown message comes back after you reset the switch and cleared it once, nobody touched the switch, or the app shows code 2801.
  • Any red alarm that returns after one clear, or a generator that did not start during an outage.
  • A battery or charger warning that will not go away.
  • The generator has been offline for days while your home network works, or the display shows a Wi-Fi module warning.
  • The exercise has not run and the unit is in AUTO.

As an authorized Generac dealer, GSHA Services diagnoses and repairs Generac home standby generators using Generac service procedures and genuine parts. We handle warranty repairs on qualifying units and perform annual maintenance so alerts do not surprise you during the next storm. Learn more about our generator repair, generator maintenance and Generac generator installation services.

Request Generac service

Tell us what the Mobile Link app is showing (a screenshot is ideal), your generator model from the data plate if you have it, and the best time to reach you. Our team will contact you to schedule a visit. For an urgent problem during an outage, please call (224) 220-3660.

Generac service area

GSHA Services is based in Woodstock, IL and services Generac generators across Chicagoland, including McHenry County and Lake County, and southeastern Wisconsin. Not sure if we cover your address? Call us or send the form above.

Related Generac codes

Frequently asked questions about Mobile Link alerts

What does “low fuel pressure” mean in the Generac Mobile Link app?

The generator’s controller is reporting that the gas pressure feeding the engine is below normal. On PowerZone 200 units it shows as Engine Fuel Delivery Pressure: code 3217 is a warning and code 3201 is an alarm that stops the unit. Evolution 2.0 lists a Fuel Pressure warning. Check that the fuel shutoff valve in the gas supply line is ON and, for propane, that the tank is not low. Do not remove panels or adjust the regulator or piping. If the supply looks fine or the alert repeats, a technician needs to measure the fuel pressure.

My app says the generator has been stopped via generator emergency shutdown switch. How do I reset it?

Find the emergency shutdown switch on the outside of the generator (the side panel on current units, the back panel on many Evolution units) and set it back to CLOSED (I). Open the lid and hold the OFF button for about three seconds until the red light stops flashing. On Evolution controllers with a display, press OFF, then ENTER instead. Then press AUTO. Do this only once. If the message comes back and nobody touched the switch, call a Generac technician.

Why does Mobile Link say my generator is offline or disconnected?

Generac’s servers have lost contact with the generator’s Wi-Fi module or cellular connectivity device. Common causes are a power outage at your router, a new router, internet provider or Wi-Fi password, a weak signal at the generator, or poor cellular coverage. It can also be a problem with the device itself, its fuse or its wiring, which a technician checks. After a network change, Evolution units with Wi-Fi can be reconnected from the WIFI menu on the display. On current units, follow the connectivity accessory’s manual or have a technician set up the connection with Field Pro.

Does an offline message mean something is wrong with my generator?

Not necessarily. Offline means the app cannot reach the generator, so it cannot show you the current status or send you alarms. The cause may be your network, the signal or the connectivity device. While it is offline, check the generator’s lights in person. On current units, a green light means it is in AUTO with utility power present, and a flashing red light means a fault. Then get the connection fixed so alerts reach you again.

Why didn’t my generator exercise this week?

The generator only exercises in AUTO, and it will not exercise if it is already running. Check the run history in the app first, since a missed notification is not always a missed exercise. If the battery was disconnected or the controller lost power, the date and time may need to be reset. On current units an internet connection keeps the clock correct; otherwise a technician resets it with Field Pro. Call us if the unit is in AUTO and still not exercising.